Plan Review Notes
Plan Review Notes For Permit 19120803
Permit Number 19120803
Review Stop P
Sequence Number 3
Notes
Date Text
2020-04-22 08:57:293RD REVIEW FBC-2017 PLUMBING
 PERMIT #19120803
 4/21/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A4.0: THE DOOR FOR THE MEN'S TOILET ROOM
 CANNOT BE REMOVED UNLESS AN ACCESSIBLE TOILET
 COMPARTMENT IS INSTALLED IN THE ROOM- SEE SECTION
 405.3.4 EXCEPTION 1 FBC P. PLEASE NOTE THAT THE
 OUTSWING DOOR THAT WAS REMOVED CAN INSWING INTO THE
 ROOM PROVIDING THE ARC OF THE DOOR COMPLIANT WITH
 SECTION 602.3.2 (2) FBC ACC.
  
 2) A4.6, DETAIL 8: THE KNEE CLEARANCE MUST EXTEND
 MINIMUM OF 8" DEEP AT 27" ABOVE THE FINISH FLOOR-
 SECTION 306.3.3 FBC ACC.
  
 3) A4.6, DETAIL 2: PROVIDE THE SHOWER GRAB LENGTHS-
 SECTION 608.3.1 AND THEIR HEIGHTS- 609.4 FBC ACC.
  
 4) A4.6, DETAIL 2: PROVIDE L-SHAPE SEAT EXTENT AND
 REQUIRED CLEARANCES PER FIGURES 610.3 AND 610.3.1 FBC
 ACC.
  
 5) P0.1 & P3.1: REFER TO COMMENT #9 FROM THE 2ND REVIEW
 AND SHOW THE CORRECT LOCATION OF THE SHUT OFF VALVE AT
 THE TOP OF THE DOWN FEED WATER PIPE TO THE WATER
 HEATER- SECTION 606.1 (5)- FBC P.
  
 6) P0.1 & P3.1: VERIFY THE RECIRCULATION PUMP IS
 EQUIPPED WITH CONTROLS THAT WILL TURN OFF THE PUMP WHEN
 THE WATER IN THE CIRCULATION LOOP HAS REACHED THE
 DESIRED TEMPERATURE, AND WHEN THERE IS NO DEMAND FOR
 HOT WATER- SECTION C404.6.1 FBC EC.
  
 7) P0.1 & P3.1: TEMPERED WATER SHALL BE DELIVERED FROM
 THE LAVATORIES THOUGH AN APPROVED TEMPERATURE LIMITING
 DEVICE THAT CONFORMS TO ASSE 1070 OR CSA B125- SECTION
 416.5 FBC P. THE MAXIMUM TEMPERATURE SHALL BE 110
 DEGREES F- SECTION 607.1.2. PLEASE SHOW THE LOCATIONS
 OF THE DEVICES ON THE DRAWINGS.
  
 8) P0.1 & P3.1: PROVIDE PIPE INSULATION SPECIFICATIONS-
 TABLE C403.2.10 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM..
  
 CHRISTOPHER L. COLE
 MECHANICAL/ PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  