Plan Review Notes
Plan Review Notes For Permit 19120803
Permit Number 19120803
Review Stop M
Sequence Number 3
Notes
Date Text
2020-04-21 16:12:203RD REVIEW FBC-2017 MECHANICAL
 PERMIT #19120803
 4/21/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS #1, 2, & 3 FROM THE 1ST AND 2ND REVIEW LISTED
 BELOW HAVE NOT BEEN COMPLETELY ADDRESSED. PLEASE PAY
 ATTENTION TO THE REMARKS BELOW THE COMMENTS IN
 CAPITALIZED LETTERS.
  
 1) SHEET M2.1: THE PLANS APPEAR TO INDICATE A NEW SHOP
 HOWEVER IT IS NOT CLEAR AS TO WHAT TYPE OF SHOP AND
 PROCESSES WILL OCCUR, WHAT PRODUCTS WILL BE FABRICATED.
 PLEASE PROVIDE A BRIEF NARRATIVE TO CLARIFY AND REFER
 TO SECTION 511 FBC M- COMPLETE PLANS AND DETAILS FOR A
 DUST COLLECTION SYSTEM ARE REQUIRED FOR WOODWORKING
 SHOPS.
 IN RESPONSE TO THE ABOVE COMMENT, THE LETTER FROM
 SCHMIDT NICHOLS TO PLANNING AND ZONING WAS SUBMITTED.
 IN PARAGRAPH 2 OF THE LETTER THE STATED USE OF THE
 SPACE IS FOR "ROOF BUILDER CONTRACTOR OPERATIONS". THIS
 STATEMENT DOES NOT CLARIFY WHAT PROCESSES WILL OCCUR IN
 THE SHOP AND WHAT MATERIALS- WOOD, METAL-PLASTICS,
 FIBERGLASS ETC.- WILL BE USED IN THOSE PROCESSES. AS
 STATED ABOVE A DUST COLLECTION SYSTEM MAY BE REQUIRED.
 THE LETTER ALSO INDICATES VEHICLE STORAGE INSIDE THE
 BUILDING.
  
 2) M6.1: CONCERNING THE EXHAUST VENTILATION SYSTEM,
 EF-4 AND IT'S SEQUENCING SHALL COMPLY WITH SECTIONS
 503.1 & 503.2 FBC M. PLEASE COMPLY AND PROVIDE
 MANUFACTURER'S SPECIFICATIONS FOR THE FAN.
  
 503.1: MOTORS AND FANS SHALL BE SIZED TO PROVIDE THE
 REQUIRED AIR MOVEMENT. MOTORS IN AREAS THAT CONTAIN
 FLAMMABLE VAPORS OR DUSTS SHALL BE OF A TYPE APPROVED
 FOR SUCH ENVIRONMENTS. A MANUALLY OPERATED REMOTE
 CONTROL INSTALLED AT AN APPROVED LOCATION SHALL BE
 PROVIDED TO SHUT OFF FANS OR BLOWERS IN FLAMMABLE VAPOR
 OR DUST SYSTEMS. ELECTRICAL EQUIPMENT AND APPLIANCES
 USED IN OPERATIONS THAT GENERATE EXPLOSIVE OR FLAMMABLE
 VAPORS, FUMES OR DUSTS SHALL BE INTERLOCKED WITH THE
 VENTILATION SYSTEM SO THAT THE EQUIPMENT AND APPLIANCES
 CANNOT BE OPERATED UNLESS THE VENTILATION FANS ARE IN
 OPERATION. MOTORS FOR FANS USED TO CONVEY FLAMMABLE
 VAPORS OR DUSTS SHALL BE LOCATED OUTSIDE THE DUCT OR
 SHALL BE PROTECTED WITH APPROVED SHIELDS AND
 DUSTPROOFING. MOTORS AND FANS SHALL BE PROVIDED WITH A
 MEANS OF ACCESS FOR SERVICING AND MAINTENANCE.
 503.2: PARTS OF FANS IN CONTACT WITH EXPLOSIVE OR
 FLAMMABLE VAPORS, FUMES OR DUSTS SHALL BE OF NONFERROUS
 OR NONSPARKING MATERIALS, OR THEIR CASING SHALL BE
 LINED OR CONSTRUCTED OF SUCH MATERIAL. WHERE THE SIZE
 AND HARDNESS OF MATERIALS PASSING THROUGH A FAN ARE
 CAPABLE OF PRODUCING A SPARK, BOTH THE FAN AND THE
 CASING SHALL BE OF NONSPARKING MATERIALS. WHERE FANS
 ARE REQUIRED TO BE SPARK RESISTANT, THEIR BEARINGS
 SHALL NOT BE WITHIN THE AIRSTREAM, AND ALL PARTS OF THE
 FAN SHALL BE GROUNDED. FANS IN SYSTEMS-HANDLING
 MATERIALS THAT ARE CAPABLE OF CLOGGING THE BLADES, AND
 FANS IN BUFFING OR WOODWORKING EXHAUST SYSTEMS, SHALL
 BE OF THE RADIAL-BLADE OR TUBE-AXIAL TYPE.
 SHEET M6.1: THE NOTES UNDER THE EF-4 SCHEDULE STATE
 THAT THE FAN AND MOTOR SHALL COMPLY WITH SECTIONS 503.1
 AND 503.2 PLEASE SHOW THE LOCATION OF THE MANUALLY
 OPERATED REMOTE CONTROL SWITCH AND PROVIDE THE SEQUENCE
 OF OPERATION FOR THE FAN.
  
 3) M2.1: THE PLANS SHOW A GARAGE DOOR POSSIBLY FOR
 LOADING AND UNLOADING OF MATERIALS, PRODUCTS, ETC.
 PLEASE INDICATE IF MOTOR VEHICLES WILL ENTER INTO, OR
 BE STORED IN THE BUILDING, AND REFER TO TABLE 403.3.1.1
 AND SECTION 404.1 FOR EXHAUST VENTILATION SYSTEM
 REQUIREMENTS.
 ACCORDING TO THE LETTER FROM SCHMIDT NICHOLS, THERE
 WILL BE VEHICLE STORAGE IN THE BUILDING. PLEASE PROVIDE
 AN EXHAUST VENTILATION SYSTEM IN THE AREAS OF VEHICLE
 STORAGE PER SECTION 404.1 AS NOTED ABOVE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER