2020-03-16 06:28:52PLUMBING 2ND REVIEW**DENIED**BUILDING A**19120803
  
  
 1) WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX. FBC-PLB
 403.2. SHT. P2.1 AND P3.1 CALL OUT BOTH TOILET ROOMS
 ARE MEN.
 2) THE SHOWER CLEAR FLOOR SPACE SHALL NOT HAVE A DOOR
 THAT SWINGS INTO IT. FBC-ACC 603.2.3
 3) SHOWER IS MISSING ON THE SANITARY ISOMETRIC DRAWING
 SHT. P2.1
 4) SHT. A4.3 SHOW TOILET CLEAR FLOOR SPACE AS 56? AND
 THAT WOULD BE CORRECT IF THE TOILET WAS WALL MOUNT.
 SHT. P.01UNDER PLUMBING FIXTURE SCHEDULE CALLS OUT
 FLOOR MOUNTED TOILET WHICH WOULD REQUIRED 59? CLEAR
 FLOOR SPACE COMPLYING WITH FBC-ACC 604.8.1.1. PLEASE
 CLARIFY FBC 107.2.1
 5) SHT. A 4.3 PLEASE SHOW THE MOUNTING OF THE MIRROR AS
 40? MAX TO THE REFLECTIVE SURFACE. FBC-ACC 603.3
 6) I WAS UNABLE TO LOCATE THE REQUIRED SERVICE SINK.
 FBC-PLB 403.1
 7) PROVIDE THE SHOWER VALVE AND HANDHELD DETAIL SHOWING
 MAX 48? TO THE GRIPPING SURFACE OF BOTH. FBC -ACC
 608.5.1
 8) SHT. A4.6 SHOW THE SHOWER AS 36? ABSOLUTE AND NOT A
 MAX. FBC-ACC 608.2.1\
 9) PROVIDE THE REQUIRED SHUT OFF VALVE ON THE WATER
 HEATER DETAIL AND WATER ISOMETRIC. ALL DOWN FEED LINES
 SHALL HAVE A SHUT OFF VALVE AND BEFORE THE EXPANSION
 TANK. FBC-PLB 606.1
  