Plan Review Notes
Plan Review Notes For Permit 19120803
Permit Number 19120803
Review Stop B
Sequence Number 2
Notes
Date Text
2020-03-11 10:52:04***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 1. APPROVED
 2. APPROVED
 3. APPROVED
 4. APPROVED
 5. APPROVED
 6. APPROVED
 7. APPROVED WITH PROVISO, AT TIME OF INSPECTION, THE
 VERTICAL CHANGE IN LEVEL (MAXIMUM 1/4") AT THE NEW DOOR
 OPENING SHALL COMPLY WITH SECTION FBC A 303.
 8. APPROVED
 9. APPROVED WITH PROVISO, PLEASE SUBMIT A CLARIFICATION
 TO TABLE ITEMS MARKED E5 AND E6 ON PAGE A5.0. THESE
 ITEMS ARE LABELED AS PRE-ENGINEERED, SHOULD HAVE BEEN
 LABELED AS PRE-FINISHED.
 10. APPROVED
 11. APPROVED
 12. APPROVED
 13. APPROVED
 14. APPROVED WITH PROVISO, THE DOORS 105A & 105B WILL
 NEED TO HAVE 48" SEPARATION IF THIS BATHROOM IS NOT
 DESIGNATED FOR ONLY ONE PERSON AT A TIME (PRIVATE). AT
 TIME OF INSPECTION PER FBC A 404.2.6. REMOVAL OF
 INTERIOR BATHROOM DOOR # 105B MAY BE REQUIRED.
 15. APPROVED
 16. APPROVED
 17. APPROVED WITH PROVISO, WHEN THERE
 IS EITHER WELDING OR BOLTING OF STRUCTURAL MEMBERS THEN
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC?B 2204.1 WELDING
 2017 FBC?B 2204.2 BOLTING.
 18. APPROVED
  
  
  