Text |
| 2020-03-11 10:52:04 | ***CORRECTIONS*** |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | FBC M = FBC MECHANICAL |
| | |
| | 2ND BUILDING REVIEW DENIED: |
| | |
| | 1. APPROVED |
| | 2. APPROVED |
| | 3. APPROVED |
| | 4. APPROVED |
| | 5. APPROVED |
| | 6. APPROVED |
| | 7. APPROVED WITH PROVISO, AT TIME OF INSPECTION, THE |
| | VERTICAL CHANGE IN LEVEL (MAXIMUM 1/4") AT THE NEW DOOR |
| | OPENING SHALL COMPLY WITH SECTION FBC A 303. |
| | 8. APPROVED |
| | 9. APPROVED WITH PROVISO, PLEASE SUBMIT A CLARIFICATION |
| | TO TABLE ITEMS MARKED E5 AND E6 ON PAGE A5.0. THESE |
| | ITEMS ARE LABELED AS PRE-ENGINEERED, SHOULD HAVE BEEN |
| | LABELED AS PRE-FINISHED. |
| | 10. APPROVED |
| | 11. APPROVED |
| | 12. APPROVED |
| | 13. APPROVED |
| | 14. APPROVED WITH PROVISO, THE DOORS 105A & 105B WILL |
| | NEED TO HAVE 48" SEPARATION IF THIS BATHROOM IS NOT |
| | DESIGNATED FOR ONLY ONE PERSON AT A TIME (PRIVATE). AT |
| | TIME OF INSPECTION PER FBC A 404.2.6. REMOVAL OF |
| | INTERIOR BATHROOM DOOR # 105B MAY BE REQUIRED. |
| | 15. APPROVED |
| | 16. APPROVED |
| | 17. APPROVED WITH PROVISO, WHEN THERE |
| | IS EITHER WELDING OR BOLTING OF STRUCTURAL MEMBERS THEN |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| | AMERICAN WELDING SOCIETY. |
| | 2017 FBC?B 2204.1 WELDING |
| | 2017 FBC?B 2204.2 BOLTING. |
| | 18. APPROVED |
| | |
| | |
| | |