Plan Review Notes
Plan Review Notes For Permit 19120803
Permit Number 19120803
Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-27 17:17:101ST REVIEW:19120803
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. DRINKING FOUNTAIN IS REQUIRED . FBC PL TABLE 403.1
 2017 FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM
 NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 2. 2017 FBC-ACCESSIBILITY CODE SECTION 602.1 DRINKING
 FOUNTAINS SHALL COMPLY WITH 307. PROTRUDING OBJECTS.
  
 3. PLEASE NOTE ON SHEET A-4.3 THE PLAN MAKES REFERENCE
 TO THE GOVERNING CODE ADAAG. THE DEPARTMENT OF JUSTICE
 HAS BLESSED THE 2017 FBC-ACCESSIBILITY CODE. THE INTENT
 AS ESTABLISHED BY S.553.502, FLORIDA STATUTES, IS TO
 MAINTAIN THE US DEPARTMENT OF JUSTICE CERTIFICATION OF
 THE CODE AS SUBSTANTIALLY EQUIVALENT TO THE ADA
 STANDARDS SO COMPLIANCE WITH THE CODE PROVIDES
 PRESUMPTION OF COMPLIANCE WITH THE ADA STANDARDS.
  
 4. DETAIL # 2 GRAB BARS ARE TO COMPLY WITH: 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 5. DETAIL # 2, THE TOILET PAPER HOLDER TO COMPLY WITH:
 2017 FBC-ACCESS. CODE 604.7 DISPENSERS. TOILET PAPER
 DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 6. PROVIDE DETAIL FOR THE TRANSFER SHOWER SHOW THE
 FOLLOWING PER FBC ACC
 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS. TRANSFER
 TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES BY 36
 INCHES CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 36 INCH WIDE
 MINIMUM ENTRY ON THE FACE OF THE SHOWER COMPARTMENT.
 CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED.
 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS. IN TRANSFER
 TYPE COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ACROSS
 THE CONTROL WALL AND BACK WALL TO A POINT 18 INCHES
 FROM THE CONTROL WALL.
 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS. IN TRANSFER
 TYPE SHOWER COMPARTMENTS, THE CONTROLS, FAUCETS, AND
 SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE SIDE WALL
 OPPOSITE THE SEAT 38 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE SHOWER FLOOR AND SHALL BE LOCATED ON
 THE CONTROL WALL 15 INCHES MAXIMUM FROM THE CENTERLINE
 OF THE SEAT TOWARD THE SHOWER OPENING.
 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE
 PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS. A
 FOLDING SEAT SHALL BE PROVIDED IN ROLL-IN TYPE SHOWERS
 REQUIRED IN TRANSIENT LODGING GUEST ROOMS WITH MOBILITY
 FEATURES COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH
 610.
 608.6 SHOWER SPRAY UNIT AND WATER.A SHOWER SPRAY UNIT
 WITH A HOSE 59 INCHES (1500 MM) LONG MINIMUM THAT CAN
 BE USED BOTH AS A FIXED-POSITION SHOWER HEAD AND AS A
 HAND-HELD SHOWER SHALL BE PROVIDED. THE SHOWER SPRAY
 UNIT SHALL HAVE AN ON/OFF CONTROL WITH A NON-POSITIVE
 SHUT-OFF. IF AN ADJUSTABLE-HEIGHT SHOWER HEAD ON A
 VERTICAL BAR IS USED, THE BAR SHALL BE INSTALLED SO AS
 NOT TO OBSTRUCT THE USE OF GRAB BARS. SHOWER SPRAY
 UNITS SHALL DELIVER WATER THAT IS 120?F (49?C) MAXIMUM.
 EXCEPTION: A FIXED SHOWER HEAD LOCATED AT 48 INCHES
 (1220 MM) MAXIMUM ABOVE THE SHOWER FINISH FLOOR SHALL
 BE PERMITTED INSTEAD OF A HAND-HELD SPRAY UNIT IN
 FACILITIES THAT ARE NOT MEDICAL CARE FACILITIES,
 LONG-TERM CARE FACILITIES, TRANSIENT LODGING GUEST
 ROOMS, OR RESIDENTIAL DWELLING UNITS.
 608.7 THRESHOLDS. THRESHOLDS IN ROLL-IN TYPE SHOWER
 COMPARTMENTS SHALL BE 1/2 INCH (13 MM) HIGH MAXIMUM IN
 ACCORDANCE WITH 303. IN TRANSFER TYPE SHOWER
 COMPARTMENTS, THRESHOLDS 1/2 INCH (13 MM) HIGH MAXIMUM
 SHALL BE BEVELED, ROUNDED, OR VERTICAL.
 EXCEPTION: A THRESHOLD 2 INCHES (51 MM) HIGH MAXIMUM
 SHALL BE PERMITTED IN TRANSFER TYPE SHOWER COMPARTMENTS
 IN EXISTING FACILITIES WHERE PROVISION OF A 1/2 INCH
 (13 MM) HIGH THRESHOLD WOULD DISTURB THE STRUCTURAL
 REINFORCEMENT OF THE FLOOR SLAB.
  
 7. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 212.2
 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 606.4 FAUCETS. CONTROLS FOR FAUCETS SHALL COMPLY WITH
 309. HAND-OPERATED METERING FAUCETS SHALL REMAIN OPEN
 FOR 10 SECONDS MINIMUM
  
 8. PLEASE PROVIDE SIZING CALCULATIONS FOR THE ROOF
 DRAINAGE PER FBC PL 1106
  
 9. OVERFLOW OR EMERGENCY ROOF DRAINS MAYBE REQUIRED IF
 PONDING WILL OCCUR ON THE ROOF IF THE MAIN ROOF
 DRAINAGE SYSTEM BECOMES CLOGGED. PER FBC PL 1106
  
 10. P3-1 THE NOTE ON THE WATER ISOMETRIC REFERS TO THE
 CIVIL PLAN I COULD NOT LOCATE ANY CIVIL PLANS PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 11. SHT A4-3 DETAIL #4 THE CLEAR FLOOR SPACE FOR THE
 WATER FOUNTAIN SHALL BE FOR A FORWARD APPROACH. PER FBC
 ACC 602.2
  
 12. THE ENERGY CALCULATIONS PAGE 7 OF 20 SHOWS THE
 WATER HEATER WITH THE EFF RATING OF .92 IT SHALL BE .98
 PER FBC ENG TABLE C404.2
  
 13.THE DOORS ENTERING THE SHOWER ROOM ARE NOT PERMITTED
 TO SWING INTO THE SPACE. PER FBC ACC 603.2.3 DOOR
 SWING.DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE
 OR CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 EXCEPTIONS:
 2.WHERE THE TOILET ROOM OR BATHING ROOM IS FOR
 INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY
 FIXTURE.
  
 14. SHT P2-1 THE BRANCH OF THE BUILDING DRAIN WITH THE
 BATHROOM GROUP , EYE WASH AND MOP SINK SHALL CONNECT TO
 MAIN BUILDING DRAIN DOWN STREAM OF THE OTHER BATHROOM
 GROUP. PER FBC PL 912.1
  
 15.SHT P3-1 LABEL THE HOT AND COLD LINES ON THE
 ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1
 ADDITIONAL INFORMATION REQUIRED.
  
 16. PLACE NOT ON PLAN BACKFLOW REQUIRED ON ICE
 MACHINES, COFFEE MAKER OR ANY OTHER APPLIANCES
 CONNECTED TO THE POTABLE WATER SYSTEMS WITH NO AIR GAP.
 PER FBC PL 608.3
  
 17. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]