Plan Review Notes
Plan Review Notes For Permit 19120803
Permit Number 19120803
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-01-15 11:20:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.0 - THERE ARE INDICATION OF INDUSTRIAL
 OCCUPANCY; HOWEVER, THERE ARE NO INDICATIONS OF THE
 TYPE OF WORK BEING PERFORMED.
  
 PLEASE PROVIDE A DETAILED NARRATIVE OF WHAT IS BEING
 MANUFACTURED, HOW IT IS RECEIVED, WHAT HAPPENS TO THE
 WASTE PRODUCTS, WHERE THE COMPLETED PRODUCT IS STORED,
 ETC?
  
  
  
 2) SHEET A 1.0 - WHAT IS THE HAZARD OF CONTENTS &
 CLASSIFICATION OF HAZARD PER NFPA 101, CH 6 OCCUPANCY
 CLASSIFICATION.
  
 PER NFPA 101, CH 6
  
 6.2 HAZARD OF CONTENTS.
 6.2.1 GENERAL.
 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF
 CONTENTS SHALL
 BE THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE,
 THE DANGER OF
 SMOKE OR GASES GENERATED, AND THE DANGER OF EXPLOSION
 OR OTHER
 OCCURRENCE POTENTIALLY ENDANGERING THE LIVES AND SAFETY
 OF THE
 OCCUPANTS OF THE BUILDING OR STRUCTURE.
 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE
 REGISTERED
 DESIGN PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE
 AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL
 ON THE BASIS
 OF THE CHARACTER OF THE CONTENTS AND THE PROCESSES OR
 OPERATIONS
 CONDUCTED IN THE BUILDING OR STRUCTURE.
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF
 HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A
 BUILDING OR STRUCTURE,
 THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION,
 UNLESS
 HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED
 IN SECTION
 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH
 43.
  
 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS.
 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY
 BUILDING OR
 STRUCTURE SHALL BE CLASSIFIED AS LOW, ORDINARY, OR HIGH
 IN
 ACCORDANCE WITH 6.2.2.2, 6.2.2.3, AND 6.2.2.4.
 6.2.2.2* LOW HAZARD CONTENTS. LOW HAZARD CONTENTS SHALL
 BE
 CLASSIFIED AS THOSE OF SUCH LOW COMBUSTIBILITY THAT NO
 SELFPROPAGATING
 FIRE THEREIN CAN OCCUR.
 6.2.2.3* ORDINARY HAZARD CONTENTS. ORDINARY HAZARD
 CONTENTS SHALL
 BE CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH
 MODERATE RAPIDITY OR
 TO GIVE OFF A CONSIDERABLE VOLUME OF SMOKE.
 6.2.2.4* HIGH HAZARD CONTENTS. HIGH HAZARD CONTENTS
 SHALL BE
 CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH
 EXTREME RAPIDITY OR FROM
 WHICH EXPLOSIONS ARE LIKELY. (FOR MEANS OF EGRESS
 REQUIREMENTS, SEE
 SECTION 7. 11.)
  
  
 3) SHEET A 4.0 - THERE ARE INDICATION OF RACKS;
 HOWEVER, THERE ARE NO RACK DETAILS.
  
 PLEASE PROVIDE ALL APPLICABLE DETAILS RELATED TO RACKS,
 INCLUDING PALLET TYPES, COMMODITY TYPE, WRAPPING TYPES,
 SHELLVING TYPES, HEIGHTS, WEIGHT LIMITS, ETC, FOR
 REVIEW PURPOSES.
  
 RACKS SHALL BE INSTALLED UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
  
  
 4) SHEET 4.0 - THERE ARE INDICATION OF STORAGE,
 HOWEVER, THERE ARE NO STORAGE DETAILS.
  
 PLEASE PROVIDE ALL APPLICABLE DETAILS RELATED TO
 STORAGE INCULDING AISLE/FLOOR LAYOUT, RACKS, INCLUDING
 PALLET TYPES, COMMODITY TYPE, WRAPPING TYPES, SHELLVING
 TYPES, HEIGHTS, WEIGHT LIMITS, ETC, FOR REVIEW
 PURPOSES.
  
 ANY PROPOSED RACKS IN THE STORAGE AREA SHALL BE
 INSTALLED UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL