Plan Review Notes
Plan Review Notes For Permit 19120803
Permit Number 19120803
Review Stop B
Sequence Number 1
Notes
Date Text
2020-01-21 15:18:182017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120803
 ADD: 2715 PINEWOOD AVE. BUILDING A
 CONT: WALKER DESIGN & CONSTRUCTION
 TEL: 561-998-0001
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 21/2020
 ACTION: DENIED
  
 1) THE VALUE OF THE PERMIT VALUE IS EXTREMELY,
 EMBRACING LOW FOR THE SCOPE OF WORK ($15,000.00).
 BEFORE THE NEXT SUBMITTAL PLEASE UPDATE THE VALUE TO AN
 APPROPRIATE VALUE FOR THE SCOPE OF WORK. OTHERWISE WE
 WILL DO A CALCULATED VALUE USING THE CURRENT ICC COST
 TABLES.
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 108.3*
 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR
 PLUMBING SYSTEMS APPEARS TO BE UNDER ESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
 2A) THIS MAYBE A TYPO, THE OCCUPANCY TYPES LISTED ON
 SHEET A1.0 THE TITLE INDEX- CODE BUILDING SHEET LIST
 THE OCCUPANCY TYPES AS BUSINESS & F1. WHEREAS ON SHEET
 A1.1 CODE AND SPECS FIRE RESISTANCE RATINGS FOR
 EXTERIOR WALLS PER TABLE 602 THE OCCUPANCY TYPES LISTED
 ARE BUSINESS AND S-1 STORAGE NOT THE F1? 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2B) SHEET A1.1 THE HEADING FOR FIRE RESISTANCE RATINGS
 FOR EXTERIOR WALLS PER TABLE 602 10 X <30 FEET LIST A 1
 HOUR FIRE RATING FOR THE EXTERIOR WALLS FOR BUSINESS
 AND S-1 STORAGE OR THE F-1 FACTORY INDUSTRIAL USE.
 PLEASE REFER TO TABLE 602, THE EXTERIOR WALLS DO NOT
 REQUIRE ANY FIRE RATING FOR THE EXTERIOR WALLS.
  
 2C) SHEET A-1.0 UNDER THE HEADING OCCUPANCY
 CLASSIFICATION FFPC SECTION 6.1.14.1.3 REFERS TO THE
 F-2 OCCUPANCY AGAIN. IS THE FACTORY/ INDUSTRIAL USE F1
 OR F2? DISCREPANCY IN PLANS.
  
 3) SHEET A-1.1 UNDER THE HEADING OF 130 CODES (B) THE
 OCCUPANCY TYPES ARE LISTED AS BUSINESS & F2 NOT THE F1
 LISTED ON SHEET A1.0. DISCREPANCY IN CODES. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) SHEET A-1.1 UNDER THE HEADING INTERIOR WALL FINISHES
 TABLE803.9 INDICATES FOR FACTORY OCCUPANCY/
 NON-SPRINKLERED UPDATE THE CORRIDOR FINISH TO C
 FINISHES NOT B PER TABLE 803.1.1 OF THE 2017 FBC-B.
  
 5A) SHEET A-1.1 INDICATES A CODE SECTION 1406.2.2 THAT
 DEALS WITH EXTERIOR WALL COVERINGS, BUT THERE IS NO
 MENTION OF THE REQUIREMENTS FOR NON-COMBUSTIBLE
 CONSTRUCTION FOR TYPE II CONSTRUCTION. SHEET S3.0 SHOWS
 THE USE OF 19/32ND INCH CDX PLYWOOD AS SUB-SHEATHING IN
 THE NEW PARAPET WALLS. THE NEW SLOPED EXTERIOR STEEL
 WALLS ALSO SHOWS 19/32ND CDX SUB-SHEATHING BEING
 INSTALLED TO THE STRUCTURAL STEEL STUDS.
 PLEASE REFER TO THE 2017 FBC-B SECTION 603.1.1
 FIRE-RETARDANT- TREATED WOOD, 1.2 NONBEARING EXTERIOR
 WALLS AND 1.3ROOF CONSTRUCTION INCLUDING FRAMING AND
 DECKING. PLEASE UPDATE THIS SHEET TO FIRE RETARDANT
 TREATED PLYWOOD.
  
 5B) SHEET S3.0 DETAIL # 1 SHOWS NEW STRUCTURAL STEEL
 STUDS 6 INCH@ 24 INCHES ON CENTER AND THE NEW SLOPED
 STEEL STUD WALL AND BRACING. IT APPEARS THERE IS NO
 SUB-SHEATHING BETWEEN THE VERTICAL FRAMING MEMBERS. IS
 THERE TO BE ANY CONNECTION BETWEEN THE 2 STRUCTURAL
 MEMBERS, ARE THEY TO ALIGN TO BE ANCHORED TOGETHER?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. DETAIL 2
 ON THE SAME SHEET SHOWS THE NEW STEEL FRAMING MEMBERS
 BEING ANCHORED INTO THE STRUCTURAL CONCRETE BEAM BUT
 THERE IS NO INFORMATION ON THE ANCHORS. DETAIL 4 THE
 SAME PAGE INDICATES THE NEW METAL ROOF FRAMING AND
 METAL ROOFING SYSTEM ARE TO BE DESIGNED BY THE
 SPECIALTY ENGINEER, IS THE SAME TO BE SAID ABOUT THE
 NEW EXTERIOR WALL SYSTEMS? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 6) THE LIFE SAFETY SHEET A4.1 SHOWS THE COMMON PATH OF
 TRAVEL IS EXCEEDED REQUIRING 2 EXITS. THE LIFE SAFETY
 PLAN DOES SHOW 2 EXITS BUT THE BACK EXIT DOES NOT SHOW
 FROM THE EXIT DISCHARGE OF THE BUILDING, THE EGRESS
 PATH TO THE PUBLIC WAY. THERE WAS NO SITE PLAN
 SUBMITTED SHOWING THE EGRESS PATH TO THE PUBLIC WAY OR
 COMPLIANCE WITH THE 2017 FBC-B 1028.5 ACCESS TO A
 PUBLIC WAY.
  
 7) NEITHER SHEET A4.0 NOR A4.1 SHOW THE GRADE
 DIFFERENCE AT EITHER EXIT DOORWAY. GOOGLE EARTH DOES
 SHOW A DROP AT THE NEW PROPOSED EXIT FROM THE BUSINESS
 OCCUPANCY.
 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
 2017 ACCESSIBILITY CODE CHANGES IN LEVEL303.2.
 VERTICAL. CHANGES IN LEVEL ARE PERMITTED IN FLOOR OR
 GROUND SURFACES, THEY SHALL COMPLY WITH 303.
  
 8) SHEET S-4.0 WIND PRESSURES, THE NEGATIVE PRESSURES
 FOR WALL ZONES 4 & 5 ARE APPROXIMATELY 3 PSF LOW FOR A
 MEAN ROOF HEIGHT OF 15 FEET, FOR EXPOSURE C AND BASED
 ON KD=0.85 USING ASCE FIGURE 30.5-1 OF ASCE 7-10. NOTE
 ROOF PRESSURES FOUND ON S-5.0 FOR ROOF ZONES 1,2 & 3
 ARE GOOD.
  
 9) SHEET A-5.0 INDICATES WITH MARKS E5, & E6 THAT THESE
 WALLS ARE PRE-ENGINEERED. IS THIS MEANT THE STRUCTURAL
 STEEL WALL FRAMING MEMBERS WERE ASSEMBLED AT A FACTORY
 LIKE ROOF TRUSSES? THERE IS ALSO HC-16 AND HR-16
 PANELS, IS THIS A PRE-MANUFACTURED WALL SYSTEM
 INCLUDING THE EXTERIOR WALL PANELS? IF SO WHO, OR WHAT
 AGENCY IS DOING THE INSPECTIONS AT THE MANUFACTURING
 SITE? 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, ACM PANELS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 11A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 11B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 11C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 12) THE PLANS ALSO INDICATE THE USE OF ACM PANELS
 PLEASE SHOW COMPLIANCE WITH 2017 FBC-B SECTIONS:
 1407.4 STRUCTURAL DESIGN,
  
 12A) MCM SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED TO
 RESIST WIND LOADS AS REQUIRED BY CHAPTER 16 FOR
 COMPONENTS AND CLADDING.
  
 12B) 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR AN
 ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE BUILDING
 OFFICIAL TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF
 CHAPTER 16 FOR WIND LOADS.
  
 12C) 1407.6 WEATHER RESISTANCE. MCM SYSTEMS SHALL
 COMPLY WITH SECTION 1403 AND SHALL BE DESIGNED AND
 CONSTRUCTED TO RESIST WIND AND RAIN IN ACCORDANCE WITH
 THIS SECTION AND THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS.
  
 12D) 1407.7 DURABILITY. MCM SYSTEMS SHALL BE
 CONSTRUCTED OF APPROVED MATERIALS THAT MAINTAIN THE
 PERFORMANCE CHARACTERISTICS REQUIRED IN SECTION 1407
 FOR THE DURATION OF USE.
  
 12E) 1407.8 FIRE-RESISTANCE RATING. WHERE MCM SYSTEMS
 ARE USED ON EXTERIOR WALLS REQUIRED TO HAVE A
 FIRE-RESISTANCE RATING IN ACCORDANCE WITH SECTION 705,
 EVIDENCE SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 THAT THE REQUIRED FIRE-RESISTANCE RATING IS MAINTAINED.
 EXCEPTION: MCM SYSTEMS NOT CONTAINING FOAM PLASTIC
 INSULATION, WHICH ARE INSTALLED ON THE OUTER SURFACE OF
 A FIRE-RESISTANCE-RATED EXTERIOR WALL IN A MANNER SUCH
 THAT THE ATTACHMENTS DO NOT PENETRATE THROUGH THE
 ENTIRE EXTERIOR WALL ASSEMBLY, SHALL NOT BE REQUIRED TO
 COMPLY WITH THIS SECTION.
  
 12F) 1407.9 SURFACE-BURNING CHARACTERISTICS. UNLESS
 OTHERWISE SPECIFIED, MCM SHALL HAVE A FLAME SPREAD
 INDEX OF 75 OR LESS AND A SMOKE-DEVELOPED INDEX OF 450
 OR LESS WHEN TESTED IN THE MAXIMUM THICKNESS INTENDED
 FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
 12G) 1407.10 TYPE I, II, III AND IV CONSTRUCTION. WHERE
 INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV
 CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS
 1407.10.1 THROUGH 1407.10.4, OR SECTION 1407.11.
  
 13) PLEASE NOTE ON SHEET A-4.3 THE PLAN MAKES REFERENCE
 TO THE GOVERNING CODE ADAAG. THE DEPARTMENT OF JUSTICE
 HAS BLESSED THE 2017 FBC-ACCESSIBILITY CODE. THE INTENT
 AS ESTABLISHED BY S.553.502, FLORIDA STATUTES, IS TO
 MAINTAIN THE US DEPARTMENT OF JUSTICE CERTIFICATION OF
 THE CODE AS SUBSTANTIALLY EQUIVALENT TO THE ADA
 STANDARDS SO COMPLIANCE WITH THE CODE PROVIDES
 PRESUMPTION OF COMPLIANCE WITH THE ADA STANDARDS.
  
 13A) DETAIL # 2 GRAB BARS ARE TO COMPLY WITH: 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 13B) DETAIL # 2, THE TOILET PAPER HOLDER TO COMPLY
 WITH: 2017 FBC-ACCESS. CODE 604.7 DISPENSERS. TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 13C)(1) THE LIFE SAFETY PLAN NOR A-4.0 SHOW DRINKING
 FOUNTAINS. PLEASE SHOW COMPLIANCE WITH THE . 2017
 FBC-ACCESSIBILITY CODE SECTION 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 13C)(2) DEPENDING ON THE LOCATION OF THE DRINKING
 FOUNTAINS THE NEED TO SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION 602.1 DRINKING FOUNTAINS
 SHALL COMPLY WITH 307. PROTRUDING OBJECTS.
  
 13D) DETAIL # 5 MAKES REFERENCES TO FACBC 11.4 THIS
 REFERENCE IS NOT TO THE CURRENT CODE SECTIONS. UNDER
 THE 2017 FBC-ACCESSIBILITY CODE THERE IS NO CHAPTER 11.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 14) SHEET A4.4 AND FIGURE 404.2.6 IS A FIGURE FOR DOORS
 IN SERIES A MINIMUM OF 4 FEET CLEAR FROM ONE DOOR LEAF
 TO ANOTHER. SHEET A-4.0 DOES NOT SHOW COMPLIANCE WITH
 THIS SECTION.
  
 15) THE SHOWER SHOWN ON SHEET A-4.0 SHOWS AN ACCESSIBLE
 SHOWER 3X3 FEET. THE SHOWER SEAT DOES NOT CONTINUE TO
 THE OUTER WALL OF THE SHOWER OR WITHIN 3 INCHES OF THIS
 WALL NOR COMPLIANCE WITH 610.3 ALSO REVIEW FIGURE
 610.3.
  
 16) SHEET A4.0 THE FLOOR PLAN SHOWS A BREAK ROOM SINK,
 THERE IS NO DETAIL FOR THIS AREA. SHEET A-6.0 DETAIL 3
 SECTION THROUGH THE BUILDING SHOWS THE ELEVATION VIEW
 OF THE SAME BREAK ROOM COUNTER AND SINK BUT THERE IS NO
 DIMENSION FOR THE SINK OR COMPLIANCE WITH: 2017
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. LAVATORIES
 AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 17) SHEETS A-6.0 AND S-3.0 BOTH SHOW THE INSTALLATION
 OF STRUCTURAL STEEL FRAMING MEMBERS AND ANCHORING OF
 ROOF FRAMING INTO THE TWIN TEE ROOF FRAMING. WHEN THERE
 IS EITHER WELDING OR BOLTING OF STRUCTURAL MEMBERS THEN
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 THE CONTRACTOR WOULD NEED TO GET A 3RD PARTY ENGINEER
 TO PROVIDE INSPECTIONS. CURRENTLY THERE ARE NO SHOP
 DRAWING SUBMITTED, CONNECTION TYPE ARE UNKNOWN.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 18) THE MECHANICAL SHEETS SHOW NEW A/C IN THE BUSINESS
 OCCUPANCY PLEASE SHOW HOW COMPLIANCE WILL BE ACHIEVED
 WITH THE 2017 ENERGY CODE SECTION C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  