| Date |
Text |
| 2020-01-07 11:37:41 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PLAN SHEET A-1: SCOPE OF WORK; NOTE 8 CALLS FOR |
| | REMOVAL OF BATHTUBS AND REPLACE WITH SHOWERS. THIS IS |
| | REINFORCED BY THE ENLARGED FLOOR PLANS AND ELEVATION |
| | PLANS ON PLAN SHEET A-3. PLAN SHEETS A-1, E-1, P-1, P-2 |
| | AND P-3 INDICATE SOME UNITS WITH SHOWERS AND SOME WITH |
| | BATHTUBS. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE |
| | ALL PLANS. |
| | 2. PER WPB FBC 107.2.1, PROVIDE ASSEMBLIES COMPLYING |
| | WITH FBC CHAPTER 7, FOR ANY PIPE PENETRATIONS THROUGH |
| | FIRE RATED FLOORS AND WALLS. |
| | 3. PLAN SHEET P-2: SELECTED WATER HEATER PROVIDES A |
| | MAXIMUM OF 2.7 GPM. THIS APPEARS NOT TO SATISFY THE |
| | REQUIREMENTS FOR HOT WATER FOR THE FIXTURES REQUIRING |
| | HOT WATER. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS |
| | FOR THE HOT WATER DEMAND AND SELECT A WATER HEATER |
| | BASED ON THE CALCULATIONS THAT WILL SATISFY THE HOT |
| | WATER REQUIREMENTS. PROVIDE MANUFACTURER'S |
| | SPECIFICATION FOR SAID WATER HEATER. PROVIDE LOCATION |
| | ON PLAN FOR THE UNIT WHICH IS ACCESSIBLE AS REQUIRED BY |
| | FBC PL 501.4. |
| | 4. PER WPB FBC 107.2.1, PROVIDE PLUMBING FIXTIURE |
| | SCHEDULE INDICATING TYPE, WATER DEMAND/WATER SUPPLY |
| | SIZE, SANITARY FIXTURE UNIT LOAD/TRAP SIZE |
| | 5. PER WPB FBC 107.2.1, PROVIDE NOTE "SHUT OFF VALVES |
| | FOR WASHER/ DRYER COMBO SHALL BE ACCESSIBLE PER FBC PL |
| | 606.3". |
| | 6. PLAN SHEET P-1 PLAN VIEW AND P-3 SANITARY RISERS; |
| | FIXTURE DRAIN FOR WASHER IS NOTED AS 3 INCH SIZE. PER |
| | FBC 2308.5.10, THIS IS PROHIBITED. FIXTURE DRAIN AND |
| | TRAP SHALL BE SIZED 2 INCH IN ACCORDANCE WITH THE |
| | MINIMUM REQUIREMENTS OF FBC PL 709.1. |
| | 7. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE ON THE |
| | SANITARY RISER DIAGRAMS THE EXISTING UNDERGROUND |
| | DRAINAGE AND VENTING SO THAT A COMPREHENSIVE REVIEW OF |
| | THE PROJECT CAN BE COMPLETED. I NOTE THAT UNIT 6 AND |
| | UNIT 7 ARE DISCHARGING INTO THE VENT STACK AND THROUGH |
| | THE VENT FOR THE GROUND FLOOR FIXTURES WHICH IS |
| | PROHIBITED. ADDITIONALLY, I NOTE THAT THERE IS NO VENT |
| | STACK SHOWN FOR UNITS 1/5 AND 4/8 WHICH IS A |
| | REQUIREMENT. WHEN ADDRESSING ALSO NOTE THAT PER FBC PL |
| | 912.2 THAT ONLY BATHROOM GROUP FIXTURES AS DEFINED IN |
| | FBC PL CHAPTER 2 MAY CONNECT TO THE WET VENT AND ONLY |
| | ON THE SAME FLOOR. |
| | 8. VALUE OF WORK APPEARS TO BE LOW. PER WPB FBC 109.3, |
| | PROVIDE DETAILED QUANTITY ESTIMATES AND/OR BONA FIDE |
| | SIGNED CONTRACTS TO MEET THE BUILDING OFFICIALS |
| | APPROVAL. VALUATION SHALL BE FOR THE TOTAL REPLACEMENT |
| | VALUE OF STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| | INTERIOR FINISHES, RELATIVE SITE WORK, ARCHITECTURAL |
| | AND DESIGN FEES. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19120794 710 10TH ST |
| | |
| | |
| | |