| Date |
Text |
| 2020-01-15 14:30:04 | |
| | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19120794 |
| | 1/15/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED. PLEASE |
| | CLARIFY IF ANY ALTERATIONS TO THE EXISTING HVAC SYSTEMS |
| | ARE PROPOSED INCLUDING KITCHEN AND BATTH EXHAUST |
| | SYSTEMS, AC SYSTEM REPLACEMENTS, OR DUCT ALTETRATIONS- |
| | SECTION 107.2.1 WPB. PLEASE NOTE THAT MECHANICAL |
| | EXHAUST IS REQUIRED FOR THE BATHS AT AN INTERMITTENT |
| | RATE OF 50 CFMS, AND FOR THE KITCHENS AT AN |
| | INTERMITTENT RATE OF 100 CFMS- TABLE 403.3.1.1 FBC M. |
| | |
| | 2) SUBMIT PRODUCT DATA SHEETS FOR ALL NEW KITCHEN |
| | APPLIANCES AND EXHAUST SYSTEMS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |