| 2019-12-18 15:51:59 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19120791 |
| | 12/18/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) WPB BUILDING DEPARTMENT RECORDS INDICATE THERE WAS A |
| | ROOFTOP PACKAGE UNIT REPLACED AT THE RESIDENCE IN 2009. |
| | THIS PERMIT IS FOR AN EXACT SAME SIZE CHANGE OUT OF A |
| | SPLIT AC SYSTEM NOT A ROOFTOP PACKAGE SYSTEM, SO IT |
| | APPEARS THIS IS A NEW SYSTEM. PLEASE PROVIDE A PLAN |
| | THAT SHOWS THE LOCATIONS OF THE NEW AIR HANDLER AND |
| | CONDENSER, AND THE REQUIRED DUCT RELOCATIONS. IF THE |
| | AIR HANDLER IS LOCATED IN A CLOSET PLEASE PROVIDE |
| | CLEARANCE MEASUREMENTS AROUND THE UNIT- SECTION |
| | M1305.1.1 FBC RES. |
| | |
| | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS- SECTION |
| | R403.6.1 FBC EC. |
| | ' |
| | 3) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION M1411.3 |
| | FBC RES. |
| | |
| | 4) PROVIDE AN ELECTRICAL PLAN- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |