2020-01-16 15:36:581ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120788
 1/16/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW SUNROOM IS DEFINED AS AN ADDITON PER SECTION
 R202 FBC EC- ADDITION. AN EXTENSION OR INCREASE IN THE
 CONDITIONED SPACE FLOOR AREA OR HEIGHT OF A BUILDING OR
 STRUCTURE. PROVIDE AN ENERGY COMPLIANCE REPORT IN
 ACCORDANCE WITH SECTIONS R101.5 FBC EC.
  
 2) HEAT IS REQUIRED IN THE NEW SUNROOM PER SECTION
 R303.10 FBC RES. CLARIFY IF A DUCT EXTENSION AND DROP
 WILL BE PROVIDED INTO THE ROOM, OR IF A NEW AC SYSTEM
 WILL BE INSTALLED FOR HEATING AND COOLING- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  