Plan Review Notes
Plan Review Notes For Permit 19120777
Permit Number 19120777
Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-14 07:28:181/14/20 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SHOW A TEMPERATURE RELIEF IN ACCORDANCE WITH
 2017 FBC M 1402.5.1.
 2. THE SYSTEM REQUIRES A FREEZE PROTECTION IN
 ACCORDANCE WITH 2017 FBC M 1402.5.3.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW