| 2020-01-14 07:28:18 | 1/14/20 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE SHOW A TEMPERATURE RELIEF IN ACCORDANCE WITH | | | 2017 FBC M 1402.5.1. | | | 2. THE SYSTEM REQUIRES A FREEZE PROTECTION IN | | | ACCORDANCE WITH 2017 FBC M 1402.5.3. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM | | | [email protected] | | | 561-701-6437 | | | |
|