Plan Review Notes
Plan Review Notes For Permit 19120727
Permit Number 19120727
Review Stop B
Sequence Number 2
Notes
Date Text
2020-02-26 16:50:34SIGN SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- ENGINEER'S DESIGN SPECIFIES A BASIC WIND SPEED OF
 160 MPH. ENGINEER NEEDS TO CLARIFY IF THIS WIND SPEED
 IS THE ULTIMATE WIND SPEED OR THE NOMINAL WIND SPEED.
 IF THIS IS THE ULTIMATE WIND SPEED, THEN ENGINEER NEEDS
 TO REVISE IT. THE ULTIMATE DESIGN WIND SPEED FOR THE
 CITY OF WEST PALM BEACH IS 170 MPH NOT 160MPH.
 SEC. 1609.1.1 FBC-BUILDING AND SEC. 120 CITY
 AMENDMENTS.
  
 RESPONSE:
 ENGINEER REVISED THE ULTIMATE WIND SPEED BUT HE ALSO
 REVISED THE BUILDING CATEGORY TO III-IV. ENGINEER TO
 CLARIFY WHY THE RISK CATEGORY WAS CHANGED FROM II TO
 III-IV. THIS WAS NOT NECESSARY. BUT IF THE ENGINEER
 WANTS TO DESIGN FOR THE III-IV RISK CATEGORY , THEN
 NEEDS TO REVISE THE ULTIMATE WIND SPEED AS REQUIRED BY
 FIGURE 1609.3(2) FBC-BUILDING. (180 MPH).
  
 2- OK.
  
 3- OK.
  
 ORIGINAL COMMENT:
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACTS INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5- NOTICE OF COMMENCEMENT WILL BE REQUIRED. SEC. 713.13
 F.S.
  
  
 -ENGINEERS-ARCHITECTS-
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,