| Plan Review Notes For Permit 19120697 |
| Permit Number |
19120697 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-22 06:49:47 | 1ST PLUMBING/GAS REVIEW**DENIED**19120697 | | | 1) PROVIDE A SITE PLAN CLEARLY SHOWING LOCATION OF | | | GENERATOR AND GENERATOR EXHAUST FROM BUILDING, WINDOWS, | | | DOORS, AND PROPERTY LINE. FBC 107.3.5 | | | 2) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, | | | TERMINATION POINT, AND ANCHORING DETAILS OF THE GAS | | | EXHAUST VENT(S) PER 2017 FBC-FUEL GAS SECS. 502 THRU | | | 505. | | | 3) IT APPEARS THE FUEL STORAGE TANK AND GENERATOR DID | | | NOT COME FROM THE FACTORY AS 1 UNIT. PLEASE CLARIFY. IF | | | NOT PLEASE PROVIDE A COMPLETE TANK TO GENERATOR FUEL | | | PIPING SHOWING MATERIAL BEING USED, SIZE FOR SUPPLY, | | | RETURN, AND VENT. FBC 107.3.5 | | | | | | TIM HUNT | | | PLUMBING PLAN REVIEW | | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | | 561-248-2703 | | | [email protected] | | | | | | |
|