Plan Review Notes
Plan Review Notes For Permit 19120697
Permit Number 19120697
Review Stop G
Sequence Number 1
Notes
Date Text
2020-01-22 06:49:471ST PLUMBING/GAS REVIEW**DENIED**19120697
 1) PROVIDE A SITE PLAN CLEARLY SHOWING LOCATION OF
 GENERATOR AND GENERATOR EXHAUST FROM BUILDING, WINDOWS,
 DOORS, AND PROPERTY LINE. FBC 107.3.5
 2) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, AND ANCHORING DETAILS OF THE GAS
 EXHAUST VENT(S) PER 2017 FBC-FUEL GAS SECS. 502 THRU
 505.
 3) IT APPEARS THE FUEL STORAGE TANK AND GENERATOR DID
 NOT COME FROM THE FACTORY AS 1 UNIT. PLEASE CLARIFY. IF
 NOT PLEASE PROVIDE A COMPLETE TANK TO GENERATOR FUEL
 PIPING SHOWING MATERIAL BEING USED, SIZE FOR SUPPLY,
 RETURN, AND VENT. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLAN REVIEW
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
  