Plan Review Notes
Plan Review Notes For Permit 19120697
Permit Number 19120697
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-12-31 11:02:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF THE EXHAUST SYSTEM.
  
 PER NFPA 110.
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME
 MOVER
 BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE
 INDEPENDENTLY
 SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR
 STRESS IS
 APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER.
  
 PLEASE DSPROVIDE THE EXHAUST SYSTEM DETAIL PER THE NFPA
 CODE.
  
  
  
 2) THERE IS NO INDIOCATION OF THE FUEL TANK VENTING.
  
 PER NFPA 110
  
 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED
 AND MAINTAINED
 IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE
 LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA
 54, NATIONAL
 FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS
 CODE.
  
 PER NFPA 30
  
 27.8.1 VENT PIPING FOR ABOVEGROUND STORAGE TANKS.
 27.8.1.1 WHERE THE OUTLETS OF VENT PIPES FOR TANKS
 STORING
 CLASS I LIQUIDS ARE ADJACENT TO BUILDINGS OR PUBLIC
 WAYS, THEY
 SHALL BE LOCATED SO THAT VAPORS ARE RELEASED AT A SAFE
 POINT
 OUTSIDE OF BUILDINGS AND NOT LESS THAN 12 FT (3.6 M)
 ABOVE THE
 ADJACENT GROUND LEVEL.
 27.8.1.2 VAPORS SHALL BE DISCHARGED UPWARD OR
 HORIZONTALLY
 AWAY FROM ADJACENT WALLS.
 27.8.1.3 VENT OUTLETS SHALL BE LOCATED SO THAT VAPORS
 WILL NOT BE
 TRAPPED BY EAVES OR OTHER OBSTRUCTIONS AND SHALL BE AT
 LEAST 5 FT
 (1.5 M) FROM BUILDING OPENINGS AND AT LEAST 15 FT (4.5
 M) FROM
 POWERED VENTILATION AIR INTAKE DEVICES.
  
 PLEASE PROVIDE DETAILS FO THE FUEL TANK VENT SYSTEM.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]