| 2019-12-31 11:02:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE NO INDICATIONS OF THE EXHAUST SYSTEM. |
| | |
| | PER NFPA 110. |
| | |
| | 7.10 EXHAUST SYSTEM. |
| | 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION, |
| | INCLUDING |
| | PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN |
| | ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION |
| | AND USE OF |
| | STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND |
| | OTHER APPLICABLE |
| | STANDARDS. |
| | 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO |
| | PREVENT |
| | EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR |
| | BUILDINGS |
| | AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT |
| | REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH |
| | WINDOWS, |
| | AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE |
| | SYSTEM. |
| | 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME |
| | MOVER |
| | BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE |
| | INDEPENDENTLY |
| | SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR |
| | STRESS IS |
| | APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER. |
| | |
| | PLEASE DSPROVIDE THE EXHAUST SYSTEM DETAIL PER THE NFPA |
| | CODE. |
| | |
| | |
| | |
| | 2) THERE IS NO INDIOCATION OF THE FUEL TANK VENTING. |
| | |
| | PER NFPA 110 |
| | |
| | 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED |
| | AND MAINTAINED |
| | IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE |
| | LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION |
| | AND USE OF |
| | STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA |
| | 54, NATIONAL |
| | FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS |
| | CODE. |
| | |
| | PER NFPA 30 |
| | |
| | 27.8.1 VENT PIPING FOR ABOVEGROUND STORAGE TANKS. |
| | 27.8.1.1 WHERE THE OUTLETS OF VENT PIPES FOR TANKS |
| | STORING |
| | CLASS I LIQUIDS ARE ADJACENT TO BUILDINGS OR PUBLIC |
| | WAYS, THEY |
| | SHALL BE LOCATED SO THAT VAPORS ARE RELEASED AT A SAFE |
| | POINT |
| | OUTSIDE OF BUILDINGS AND NOT LESS THAN 12 FT (3.6 M) |
| | ABOVE THE |
| | ADJACENT GROUND LEVEL. |
| | 27.8.1.2 VAPORS SHALL BE DISCHARGED UPWARD OR |
| | HORIZONTALLY |
| | AWAY FROM ADJACENT WALLS. |
| | 27.8.1.3 VENT OUTLETS SHALL BE LOCATED SO THAT VAPORS |
| | WILL NOT BE |
| | TRAPPED BY EAVES OR OTHER OBSTRUCTIONS AND SHALL BE AT |
| | LEAST 5 FT |
| | (1.5 M) FROM BUILDING OPENINGS AND AT LEAST 15 FT (4.5 |
| | M) FROM |
| | POWERED VENTILATION AIR INTAKE DEVICES. |
| | |
| | PLEASE PROVIDE DETAILS FO THE FUEL TANK VENT SYSTEM. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |