| Plan Review Notes For Permit 19120697 |
| Permit Number |
19120697 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-01-21 15:32:18 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE STRUCTURAL DRAWINGS FOR THE EXACT | | | INSTALLATION DETAILS FOR ANCHORING THE GENERATOR | | | STRUCTURAL SUPPORTS TO THE CONCRETE FLOOR SLAB AS | | | INDICATED ON THE GENERATOR DETAIL ON SHEET E-0.03. FBC | | | 107.2.1 | | | | | | 2) THE STRUCTURAL ENGINEER IS TO VERIFY THAT THE 4" | | | THICK CONCRETE SLAB ON GRADE THAT IS SHOWN ON THE | | | BUILDING PLANS IS ADEQUATE TO SUPPORT THE GRAVITY LOADS | | | OF THE GENERATOR SET. PROVIDE CALCULATIONS. FBC | | | 107.2.1.2 |
|