| 2020-02-21 11:19:04 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| | 109.3 (NOT PROVIDED,) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. METER MAIN PANEL SCHEDULE SHOWS A WIRE SIZE OF #0/0 |
| | ON A 200 AMP BREAKER. THIS WIRE SIZE DOES NOT EXIST. |
| | PLEASE CLARIFY THE WIRE SIZE IS SUFFICIENT FOR THE 200 |
| | AMP BREAKER. ADDITIONALLY, THIS IS SHOWN FEEDING A 150 |
| | AMP PANEL. A 200 AMP FEED CANNOT FEED A PANEL THAT IS |
| | RATED FOR ONLY 150 AMPS. PROVIDE CLARIFICATIONS AND/OR |
| | CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC |
| | 310.15(B)(16), 408.30 (PANEL SCHEDULE FOR METER MAIN |
| | STILL SHOWS A 200 AMP BREAKER FEEDING THE INTERIOR |
| | PANEL. IF THIS IS A 200 AMP BREAKER, THE WIRE WOULD |
| | NEED TO BE AT LEAST RATED FOR 200 AMPS, AND THE PANEL |
| | WOULD NEED TO BE RATED FOR AT LEAST 200 AMPS. PROVIDE |
| | CLARIFIATIONS AND/OR CORRECTIONS AS NEEDED.) |
| | 7. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |