2020-02-21 11:19:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED,)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. METER MAIN PANEL SCHEDULE SHOWS A WIRE SIZE OF #0/0
 ON A 200 AMP BREAKER. THIS WIRE SIZE DOES NOT EXIST.
 PLEASE CLARIFY THE WIRE SIZE IS SUFFICIENT FOR THE 200
 AMP BREAKER. ADDITIONALLY, THIS IS SHOWN FEEDING A 150
 AMP PANEL. A 200 AMP FEED CANNOT FEED A PANEL THAT IS
 RATED FOR ONLY 150 AMPS. PROVIDE CLARIFICATIONS AND/OR
 CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC
 310.15(B)(16), 408.30 (PANEL SCHEDULE FOR METER MAIN
 STILL SHOWS A 200 AMP BREAKER FEEDING THE INTERIOR
 PANEL. IF THIS IS A 200 AMP BREAKER, THE WIRE WOULD
 NEED TO BE AT LEAST RATED FOR 200 AMPS, AND THE PANEL
 WOULD NEED TO BE RATED FOR AT LEAST 200 AMPS. PROVIDE
 CLARIFIATIONS AND/OR CORRECTIONS AS NEEDED.)
 7. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER