| Date |
Text |
| 2019-12-31 11:32:03 | 1) THE GAS LANTERNS SHALL BE LISTED AND LABELED PER |
| | 2017 FBC-RESIDENTIAL SEC. G2404.3.SUBMIT MANUFACTURER |
| | SPECIFICATIONS THAT SHOW THE UNITS COMPLY. |
| | 2) ) INSTALLATIONS WITHIN 10 FT (3 M) OF A PUBLIC |
| | VEHICULAR THOROUGHFARE OR DESIGNATED PARKING LOCATION |
| | SHALL BE PROVIDED WITH VEHICULAR BARRIER PROTECTION FOR |
| | THE CONTAINER'S FITTING HOUSING, HOUSING COVER, |
| | CONTAINER CONNECTIONS, AND PIPING. NFPA 58-14 SEC. |
| | 6.6.6.1 (C). |
| | 3) SHOW THE DISTANCE OF THE LP TANK FROM THE EXTERIOR |
| | WALL OF THE STRUCTURE ON THE SURVEY. COMPLY WITH NFPA |
| | 58 SEC.6.3.2.3. |
| | 4) PAGES/ SIZING TABLE FROM THE 2011 EDITION OF NFPA 58 |
| | HAVE BEEN SUBMITTED. THE 2014 EDITION HAS BEEN ADOPTED |
| | BY THE 2017 FBC. SUBMIT THE REQUIRED PAGES FROM THE |
| | 2014 EDITION OF NFPA 58. |
| | 5) THE SUBMITTED SPEC SHEET FOR THE BELOW GROUND EARTH |
| | AUGERS IS UNACCEPTABLE. THE SUBMITTED SHEET BEARS A |
| | PHOTOCOPY OF AN ENGINEER'S SIGNATURE. THIS IS IN |
| | VIOLATION OF FL. ADMIN. CODE RULE 61G15-23.001. |
| | 6) SUBMIT CLEAR AND LEGIBLE SHEETS FOR THE GAS |
| | REGULATORS. SOME OF THE PRINTING IS SO LIGHT ON THE |
| | SHEET IT IS ILLEGIBLE. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GRILL. |
| | THE GRILL SHALL BE LISTED AND LABELED. 2017 |
| | FBC-RESIDENTIAL SEC. G2404.3. |
| | 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLE |
| | USED TO SIZE THE LOW PRESSURE SIDE OF THE GAS SYSTEM OR |
| | PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH |
| | SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD |
| | THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER |
| | TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND |
| | TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. |
| | 9) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE |
| | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP |
| | REGULATOR. 2017 FBC-RES. SEC. G2421.2 (7). |
| | 10) CLEARLY SHOW THE DISTANCE OF THE TANK FROM THE |
| | EXTERIOR BUILDING WALL AND ADJACENT PROPERTY LINES, THE |
| | DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, |
| | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY |
| | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK |
| | PER NFPA 58, TABLE 3-2.2.2. |
| | 11) AT INSTALLATIONS WITHIN 10 FT (3 M) OF A PUBLIC |
| | VEHICULAR THOROUGHFARE OR DESIGNATED PARKING LOCATION, |
| | A NONINTERCHANGEABLE UNDERGROUND CONTAINER SHALL BE |
| | INSTALLED 18 IN. (460 MM) BELOW GRADE OR VEHICULAR |
| | BARRIER PROTECTION SHALL BE PROVIDED. NFPA 58 SEC. |
| | 6.6.6.1. |
| | 12) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER |
| | NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE |
| | MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS |
| | ON THE TYPE OF CATHODIC PROTECTION, SIZE ( LBS) & |
| | NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |