Plan Review Notes
Plan Review Notes For Permit 19120638
Permit Number 19120638
Review Stop G
Sequence Number 1
Notes
Date Text
2019-12-31 11:32:031) THE GAS LANTERNS SHALL BE LISTED AND LABELED PER
 2017 FBC-RESIDENTIAL SEC. G2404.3.SUBMIT MANUFACTURER
 SPECIFICATIONS THAT SHOW THE UNITS COMPLY.
 2) ) INSTALLATIONS WITHIN 10 FT (3 M) OF A PUBLIC
 VEHICULAR THOROUGHFARE OR DESIGNATED PARKING LOCATION
 SHALL BE PROVIDED WITH VEHICULAR BARRIER PROTECTION FOR
 THE CONTAINER'S FITTING HOUSING, HOUSING COVER,
 CONTAINER CONNECTIONS, AND PIPING. NFPA 58-14 SEC.
 6.6.6.1 (C).
 3) SHOW THE DISTANCE OF THE LP TANK FROM THE EXTERIOR
 WALL OF THE STRUCTURE ON THE SURVEY. COMPLY WITH NFPA
 58 SEC.6.3.2.3.
 4) PAGES/ SIZING TABLE FROM THE 2011 EDITION OF NFPA 58
 HAVE BEEN SUBMITTED. THE 2014 EDITION HAS BEEN ADOPTED
 BY THE 2017 FBC. SUBMIT THE REQUIRED PAGES FROM THE
 2014 EDITION OF NFPA 58.
 5) THE SUBMITTED SPEC SHEET FOR THE BELOW GROUND EARTH
 AUGERS IS UNACCEPTABLE. THE SUBMITTED SHEET BEARS A
 PHOTOCOPY OF AN ENGINEER'S SIGNATURE. THIS IS IN
 VIOLATION OF FL. ADMIN. CODE RULE 61G15-23.001.
 6) SUBMIT CLEAR AND LEGIBLE SHEETS FOR THE GAS
 REGULATORS. SOME OF THE PRINTING IS SO LIGHT ON THE
 SHEET IT IS ILLEGIBLE. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GRILL.
 THE GRILL SHALL BE LISTED AND LABELED. 2017
 FBC-RESIDENTIAL SEC. G2404.3.
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLE
 USED TO SIZE THE LOW PRESSURE SIDE OF THE GAS SYSTEM OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
 9) WHERE CONNECTED TO RIDGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-RES. SEC. G2421.2 (7).
 10) CLEARLY SHOW THE DISTANCE OF THE TANK FROM THE
 EXTERIOR BUILDING WALL AND ADJACENT PROPERTY LINES, THE
 DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
 11) AT INSTALLATIONS WITHIN 10 FT (3 M) OF A PUBLIC
 VEHICULAR THOROUGHFARE OR DESIGNATED PARKING LOCATION,
 A NONINTERCHANGEABLE UNDERGROUND CONTAINER SHALL BE
 INSTALLED 18 IN. (460 MM) BELOW GRADE OR VEHICULAR
 BARRIER PROTECTION SHALL BE PROVIDED. NFPA 58 SEC.
 6.6.6.1.
 12) A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE ( LBS) &
 NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  