| Plan Review Notes For Permit 19120609 |
| Permit Number |
19120609 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-05-18 12:28:07 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE RESPONSE LETTER STATES THAT THE DISTANCE FROM | | | THE NORTH WALL OF THE FULLY SPRINKLERED BUILDING TO THE | | | CENTER LINE OF THE ALLEY IS 7'-2". BY THE DEFINITION IN | | | FBC SECTION 202, THIS IS THE FIRE SEPARATION DISTANCE. | | | FOR A FIRE SEPARATION DISTANCE OF 5 FEET TO LESS THAN | | | 10 FEET FOR A FULLY SPRINKLERED BUILDING, FBC TABLE | | | 705.8 LISTS THE AREA OF ALLOWABLE OPENINGS AS 25 | | | PERCENT OF THE WALL AREA PER STOREY. ITEM #6 OF THE | | | RESPONSE LETTER AND SHEET A-2 OF THE PLANS HAVE THE | | | ALLOWABLE AREA AS 45 PERCENT. PLEASE CORRECT. | | | | | | 2) THE PROPOSED GLAZING ANALYSIS ON SHEET A-2, | | | SPECIFIES THE TOTAL OF NEW GLAZING AND DOES NOT INCLUDE | | | EXISTING OPENINGS. WHEN DETERMINING TO PERCENTAGE OF | | | ALLOWABLE OPENINGS FOR STOREY OF A BUILDING, YOU ARE | | | REQUIRED TO INCLUDE ALL OPENINGS (NEW AND EXISTING), | | | EVEN THOSE THAT DON'T HAVE GLAZING. FBC 705.8 | | | | | | 3) IN ORDER TO SPEED YOUR PLAN REVIEW, IT IS HELPFUL TO | | | PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM. |
|