2020-01-24 18:04:34PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) REPEAT COMMENT. SHEET 4 OF 5 OF PRODUCT APPROVAL
 FL11291-R7 REQUIRES A 3-1/2" EDGE DISTANCE FOR THE
 ANCHOR SPACING OF 12" LISTED IN THE TABLE. A 3" EDGE
 DISTANCE IS SPECIFIED IN THE INSTALLATION SCHEDULE THAT
 WAS SUBMITTED. THE NOTES THAT ARE BELOW THE TABLE
 REQUIRE THE ANCHOR SPACING IN THE TABLE TO BE
 MULTIPLIED BY .86 WHEN THE EDGE DISTANCE IS 3".
 THEREFORE THE SPACING WOULD BE 10.32 " WHICH IS 12" X
 .86. PLEASE CORRECT.
  
 2) THE TABLE FROM THE STORM CATCHER THAT IS MARKED IS
 TABLE 4 WHICH IS FOR CONCRETE. THE INSTALLATION
 SCHEDULE YOU SUBMITTED SPECIFIES THAT THE SUBSTRATE IS
 CONCRETE BLOCK. TABLE 16 ON PAGE 25 IS FOR HOLLOW
 CONCRETE BLOCK AND TABLE 12 ON PAGE 21 IS FOR GROUT
 FILLED CONCRETE BLOCK. USE THE TABLE THAT MATCHES THE
 SUBSTRATE THAT YOU WILL BE ANCHORING TO. IF IT IS
 POURED CONCRETE YOU WILL NEED TO CHANGE THE
 INSTALLATION SCHEDULE FROM CONCRETE BLOCK TO CONCRETE.
 IT IS NOT CLEAR WHICH METHOD OF ATTACHMENT WILL BE USED
 TO INSTALL THE STORM CATCHER ABATEMENT SCREEN SYSTEM.
 THERE ARE SEVERAL DIFFERENT WAYS TO ATTACH THE FABRIC
 TO THE STRUCTURE SHOWN IN THE PRODUCT APPROVAL. CIRCLE
 THE APPROPRIATE ITEMS IN THE PRODUCT APPROVAL AND
 PROVIDE A DIAGRAM DRAWING THAT CLEARLY SHOWS HOW THE
 FABRIC WILL BE INSTALLED. FBC 107.2.1
  