2020-01-16 18:49:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHEET 4 OF 5 OF PRODUCT APPROVAL FL11291-R7 REQUIRES
 A 3-1/2" EDGE DISTANCE FOR THE ANCHOR SPACING OF 12"
 LISTED IN THE TABLE. A 3" EDGE DISTANCE IS SPECIFIED IN
 THE INSTALLATION SCHEDULE THAT WAS SUBMITTED. THE NOTES
 THAT ARE BELOW THE TABLE REQUIRES THE ANCHOR SPACING IN
 THE TABLE TO BE MULTIPLIED BY .86 WHEN THE EDGE
 DISTANCE IS 3". THEREFORE THE SPACING WOULD BE 10.32 "
 WHICH IS 12" X .86. PLEASE CORRECT.
  
 2) IT IS NOT CLEAR WHICH METHOD OF ATTACHMENT WILL BE
 USED TO INSTALL THE STORM CATCHER ABATEMENT SCREEN
 SYSTEM. THERE ARE SEVERAL DIFFERENT WAYS TO ATTACH THE
 FABRIC TO THE STRUCTURE SHOWN IN THE PRODUCT APPROVAL.
 CIRCLE THE APPROPRIATE ITEMS IN THE PRODUCT APPROVAL
 AND PROVIDE A DIAGRAM DRAWING THAT CLEARLY SHOWS HOW
 THE FABRIC WILL BE INSTALLED. FBC 107.2.1
  