Plan Review Notes
Plan Review Notes For Permit 19120578
Permit Number 19120578
Review Stop P
Sequence Number 1
Notes
Date Text
2019-12-31 15:11:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PER FBC PL 403.3.1, THE ROUTE TO THE PUBLIC TOILET
 FACILITIES REQUIRED BY SECTION 403.3 SHALL NOT PASS
 THROUGH KITCHENS, STORAGE ROOMS OR CLOSETS.
 2. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE
 SANITARY AND WATER RISER DIAGRAMS REFLECTING THE SCOPE
 OF WORK
 3. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE A
 DETAIL FOR THE WATER HEATER SHOWING COMPLIANCE WITH THE
 REQUIREMENTS OF FBC PL 503.1, 504.1/504.2, 504.4,
 504.6, 504.7.2 AND 607.3. SPECIFICALLY PROVIDE ROUTING
 AND TERMINATION OF THE PAN DRAIN, IF DISCHARGING TO
 SANITARY THEN MAKE PROVISION IN THE SANITARY DRAWINGS,
 PROVIDING A TRAPPED AND VENTED OPEN RECEPTACLE PER FBC
 PL 802.3; PROVIDE TRAP SEAL PROTECTION TO COMPLY WITH
 FBC PL 1002.4.1 THROUGH 1002.4.1.4. WATER HEATER SHALL
 BE LOCATED AND CONNECTED SO AS TO PROVIDE ACCESS FOR
 OBSERVATION, MAINTENANCE, SERVICING AND REPLACEMENT PER
 FBC PL 501.4.
 4. PER FBC PL 416.5, TEMPERED WATER SHALL BE DELIVERED
 FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN
 PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS,
 PATRONS AND VISITORS. TEMPERED WATER SHALL BE DELIVERED
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070
 5. PROVIDE WATER HAMMER ARRESTOR CONFORMING TO ASSE
 1010 FOR REFRIGERATOR WATER CONNECTION PER FBC PL
 604.9.
 6. PROVIDE INDIVIDUAL SHUT OFF FOR EACH, SINK AND
 REFRIGERATOR PER FBC PL 606.2.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  