| 2019-12-31 12:53:18 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19120578 |
| | 12/31/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW RTU IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 2) M101: AN AUTOMATIC O/A SHUTOFF DAMPER- EITHER |
| | MOTORIZED OR GRAVITY- SHALL BE PROVIDED FOR THE RTU- |
| | SECTION C403.2.4.3 FBC EC. |
| | |
| | 3) M101: A DUCT SMOKE DETECTOR IS REQUIRED IN THE |
| | SUPPLY AIR SYSTEM OF THE 5-TON RTU PER SECTION 606.2.1 |
| | FBC M. ALTHOUGH THESCHEDULE INDICATES 1750 CFM'S OF |
| | SUPPLY AIR, TRANE PERFORMANCE DATA FOR THE UNIT |
| | INDICATES IT CAN PRODUCE OVER 2000 CFMS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |