Plan Review Notes
Plan Review Notes For Permit 19120578
Permit Number 19120578
Review Stop B
Sequence Number 1
Notes
Date Text
2020-01-07 13:54:282017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19120578
 ADD: 2500 METROCENTRE BLVD. SUITE: 06
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 07/2020
 ACTION: DENIED
  
 1) SHEET A-6.00:
 1A) DETAIL # 2 THE HEIGHT OF THE MIRROR IS INDICATED TO
 BE 40 INCHES FROM THE BOTTOM OF THE MIRROR FRAME.
 PLEASE NOTE THE 40 INCHES MAXIMUM HEIGHT IS TAKEN FROM
 FINISH FLOOR TO THE BOTTOM OF THE REFLECTIVE SURFACE.
 2017 FBC-ACCESSIBILITY CODE 603.3 MIRRORS. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 1B) DETAIL # 3 IS OF THE SIDE WALL OF THE RESTROOM. THE
 ISSUE HERE IS THE DIMENSIONS FOR THE TOILET PAPER
 HOLDER. 2017 FBC-ACCESS. CODE 604.7 DISPENSERS. TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER.
  
 2) SHEET M101 & M501:
  
 2A) UNDER THE HEADING FOR NEW ROOF TOP EXHAUST FANS
 EF-1 THE PLANS STATE THAT A NEW CURB AND EXHAUST FAN
 ARE TO BE INSTALLED. SHEET M501 NOTES 5 & 6 THAT THE
 NEW ROOFTOP ARE TO ADHERE TO HURRICANE CODE
 REQUIREMENTS REQUIRING ROOF TIE-INS AND WIND
 RESISTANCE. HOW DO YOU KNOW WHAT IS REQUIRED SINCE
 THERE IS NO WIND DESIGN CRITERIA, WIND SPEED ETC.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 2B) SHEET M101. NOTES FOR THE RTU-1 UNDER REMARKS STATE
 THE NEW RTU CURB IS TO BE FACTORY PROVIDED 14 INCH WIND
 LOAD RATED CURB.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS,
 (G) PRE-ENGINEERED A/C STANDS
  
 2C) SHEET M501 DETAIL #6 SHOWS A ROOF FRAMING DETAIL
 BUT THE DETAIL IS GENERIC. THE PLAN DOES NOT STATE THE
 SIZE OF THE INFILL FRAMING STEEL NOR DOES THE PLAN
 INDICATE IF THE STEEL L-ANGLE IS TO BE WELDED TO THE
 TOP CHORD OF THE BAR JOIST.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FRAMING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 2D) SHEET M501 DETAIL # 2 ALSO NOTES FOR THE NEW STEEL
 INFILL FRAMING SEE STRUCTURAL DRAWINGS, THERE ARE NO
 STRUCTURAL DRAWING WITHIN THE SUBMITTED SET OF PLANS.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FRAMING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 2E) SHEET M501 DETAIL # 2 INDICATES THE USE OF 2 INCH
 STEEL STRAPS TO ANCHOR THE RTU TO THE CURB, GENERIC
 DETAIL, FOR THE 170 VULT WIND HOW MANY ANCHORS WILL BE
 REQUIRED. LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS, RTUS, FANS OR A/C
 STANDS, AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF
 FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF STAND
 TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  