| 2020-01-08 09:49:37 | RE STRIPPING BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1- SCOPE OF WORK IS NOT CLEAR. THIS IS A MULTI LEVEL |
| | BUILDING. ONLY ONE FLOOR LEVEL WAS SUBMITTED. IF THE |
| | SCOPE OF WORK IS FOR MORE THAN ONE LEVEL, THEN PROVIDE |
| | FLOOR PLAN FOR EACH LEVEL WHERE WORK IS GOING TO TAKE |
| | PLACE. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- CLEARLY IDENTIFY HOW MANY PARKING SPACES ARE |
| | PROVIDED ON EACH LEVEL TO VERIFY COMPLIANCE WITH THE |
| | MINIMUM ACCESSIBLE PARKING SPACES. NOTE: 1 TO 25 |
| | PARKING SPACES REQUIRE AT LEAST 1 ACCESSIBLE SPACE. |
| | AND, 26 TO 50 PARKING SPACES REQUIRE AT EAST 2 |
| | ACCESSIBLE PARKING SPACES. SEC. 801.3 FBC-EXISTING |
| | BUILDING AND TABLE 208.2 FBC-ACCESSIBILITY. |
| | |
| | 3- PLANS SUBMITTED NEED TO HAVE THE SEAL AND SIGNATURE |
| | OF THE ENGINEER SHOWN ON THE TITLE BLOCK AS REQUIRED BY |
| | CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | |
| | 4- PLANS SUBMITTED ARE TOO SMALL. THEY ARE NOT LEGIBLE. |
| | PROVIDE LARGER DRAWINGS THAT HAVE THE ACTUAL SCALE |
| | SHOWN ON PLANS. SEC. 107.2.1 AND SEC. 107.2.1.3 CITY |
| | AMENDMENTS. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |