| Plan Review Notes For Permit 19120571 |
| Permit Number |
19120571 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2020-07-14 13:44:33 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 4TH MECHANICAL REVIEW DENIED: | | | | | | FBC M 602.1 - 602.2, PLEASE PROVIDE THE DOOR DETAILS | | | FOR THE AIR HANDLER CLOSET AS THIS CLOSET APPEARS TO BE | | | A PLENUM. | | | | | | | | | PROVISOS: | | | | | | 1) IF THE WELDING OPTION IS SELECTED FOR THE RTU STAND | | | CONNECTIONS THE FOLLOWING ARE REQUIRED TO BE APPROVED | | | BY THE DESIGNER OF RECORD: | | | AWS D1.1 CLAUSE 3.1: AT TIME OF INSPECTION PLEASE | | | PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. | | | SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: | | | BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO | | | BE USED. | | | AWS D1.1 CLAUSE 4.15: AT TIME OF INSPECTION PLEASE | | | PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE | | | W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO | | | VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS | | | IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. | | | | | | 2) AS PER SECTION FBC M 508.1.1, THE TEMPERATURE | | | DIFFERENTIAL BETWEEN THE MAKE-UP AIR AND THE | | | CONDITIONED SPACE MUST NOT EXCEED 10 DEGREES F. | | | | | | | | | | | | |
|