| Date |
Text |
| 2020-01-06 14:15:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. PER WPB FBC 107.2.1, PROVIDE SIZING PROCEDURE AND |
| | CALCULATIONS AS CALLED OUT IN STD. PDI-G101 USED IN |
| | DETERMINING THE GB-75 INTERCEPTOR. |
| | 2. THE SPECIFIED FL1170 DOES NOT COMPLY WITH ASSE 1070 |
| | AS REQUIRED BY FBC PL 416.5. PER WPB FBC 107.2.1, |
| | REVISE AND RESUBMIT. |
| | 3. SPECIFY THAT A WATER TEMPERING DEVICE SHALL BE |
| | FURNISHED FOR THE LAVATORY IN ACCORDANCE WITH FBC PL |
| | 416.5. |
| | 4. PER WPB FBC 107.2.1, SPECIFY THE TANKLESS WATER |
| | HEATER AT THE LAVATORY AND PROVIDE MANUFACTURER?S |
| | SPECIFICATION FOR THE SAME. |
| | 5. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| | SPECIFICATION FOR THE GAS TANKLESS WATER HEATER. |
| | 6. WATER RISER MISTAKENLY IDENTIFIES SECTIONS OF COLD |
| | WATER DISTRIBUTION AS HOT WATER WHICH IS FEEDING THE |
| | TANKLESS WATER HEATER AS WELL AS THE HAND SINK AND MOP |
| | SINK. EFFECTIVELY THERE IS NO HOT WATER TO THE HAND |
| | SINK OR MOP SINK. PER WPB FBC 107.2.1, CORRECT AND |
| | RESUBMIT. ADDITIONALLY, SHOW THE EXISTING COLD WATER |
| | SUPPLY TO THE EXISTING BATHROOM. |
| | 7. PLAN PAGE 3.0P GAS INSTA-HOT WATER HEATER DETAIL HAS |
| | TWO NOTES: 1)WATER HEATER SET TO 140 DEGREES FOR |
| | WAREWASH ONLY; 1)WATER HEATER SET TO 110 DEGREES FOR |
| | HAND AND PREP SINKS ONLY. PER WPB FBC 107.2.1, PLEASE |
| | CLARIFY. |
| | 8. PER WPB FBC 107.2.1, SPECIFY FAUCET FOR MOP SINK |
| | WHICH COMPLIES WITH FBC PL 608.2 BACKFLOW PROTECTION. |
| | 9. PER WPB FBC 107.2.1, PROVIDE BACKFLOW PROTECTION IN |
| | COLD WATER SUPPLY TO THE ICEMAKER TO COMPLY WITH FBC PL |
| | 608.3. |
| | 10. PLAN SHEET 1.1A KITCHEN EQUIPMENT SCHEDULE; ITEM |
| | 16, WAREWASHER (DISHWASHER) CALLS FOR A 2 INCH INDIRECT |
| | WASTE. PER WPB FBC 107.2.1, INDICATE ON THE SANITARY |
| | ISOMETRIC THAT INDIRECT WASTE AND WHERE IT DISCHARGES |
| | TO. COMPLY WITH FBC PL 802.1.7. ADDITIONALLY, INSURE |
| | THAT THE QUANTITY AND THE LOCATIONS OF FLOOR SINKS ARE |
| | THE SAME ON BOTH RISER AND FLOOR PLAN. |
| | 11. A VENTED TRAP HAS BEEN PROVIDED AND IDENTIFIED AS A |
| | FLOOR SINK/ DR (DISHTABLE?). THE EQUIPMENT SCHEDULE |
| | CALL FOR A 1-1/2 INCH DIRECT CONNECTION TO THE |
| | SANITARY. PER WPB FBC 107.2.1, CLARIFY THAT THE VENTED |
| | TRAP IS PROVIDING THA AND IS NOT THE FLOOR SINK FOR THE |
| | DISHWASHER. |
| | 12. PER WPB FBC 107.2.1, PROVIDE INDIVIDUAL INDIRECT |
| | WASTE FROM EACH WELL OF THE THREE-COMPARTMENT SINK |
| | DISCHARGING INDEPENDENTLY TO THE FLOOR SINK TO COMPLY |
| | FBC FL 802.1. |
| | 13. PER WPB FBC 107.2.1, CLEARLY INDICATE HOW THE |
| | DISPOSAL OF COOLER AND FREEZER EVAPORATOR CONDENSATE |
| | WILL BE HANDLED. |
| | 14. IF OCCUPANCY A-2 AND OCCUPANT LOAD CALCULATION IS |
| | NOT DISPUTED BY THE BUILDING PLANS EXAMINER, THEN THE |
| | FIXTURE REQUIREMENTS PER FBC PL SECTION 403 ARE |
| | COMPLIED WITH. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19120571 7310 GEORGIA AVE # 1 |
| | |