2020-01-03 10:41:081) THE CSST LINE TO K27 IS UNDERSIZED PER THE
 REFERENCED TABLE ON THE PLANS.
 2) SIZE THE GAS MANIFOLD IN ITS ENTIRETY TO ITEMS # K5,
 K7, & K33.
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE KITCHEN
 APPLIANCES. IF COMBUSTION AIR IS PROVIDD BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2014 FBC-FUEL
 GAS SEC.304.1, 304.9.3.
  