| Notes |
| Date |
Text |
| 2020-01-03 10:41:08 | 1) THE CSST LINE TO K27 IS UNDERSIZED PER THE | | | REFERENCED TABLE ON THE PLANS. | | | 2) SIZE THE GAS MANIFOLD IN ITS ENTIRETY TO ITEMS # K5, | | | K7, & K33. | | | 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE KITCHEN | | | APPLIANCES. IF COMBUSTION AIR IS PROVIDD BY THE | | | BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM | | | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN | | | ADDITION TO THE REQUIRED VENTILATION AIR. 2014 FBC-FUEL | | | GAS SEC.304.1, 304.9.3. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|