| Plan Review Notes For Permit 19120501 |
| Permit Number |
19120501 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-04-28 11:27:55 | NEW BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PRODUCT APPROVAL (14-1204.10) LISTED ON DRAWING | | | A-6.0 FOR THE STOREFRONT GLAZING DOES NOT MEET IMPACT | | | REQUIREMENTS FBC 1609.1.2 - PLEASE PROVIDE PRODUCT | | | APPROVAL NUMBER FOR THE REQUIRED SHUTTERS. | | | 2) PLEASE PROVIDE PRODUCT APPROVAL FOR THE METAL | | | ROOFING. | | | 3) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT | | | (GEOTECHNICAL REPORT) TO VERIFY THE REQUIRED SOIL | | | BEARING CAPACITY PER DRAWINGS. | | | 4) PLEASE PROVIDE SIGNED AND SEALED SIDING ATTACHMENT | | | DETAILS OR PRODUCT APPROVAL TO COMPLY WITH WIND DESIGN | | | PRESSURES SHOWN ON THE DRAWINGS. | | | 5) PLEASE PROVIDE SIGNED AND SEALED LOUVER SYSTEM | | | DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. | | | 6) PLEASE PROVIDE SIGNED AND SEALED METAL CANOPY | | | DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. | | | 7) COVER SHEET SHOWS CODE USED "RESIDENTIAL" SHOULD BE | | | "BUILDING". | | | |
|