| Plan Review Notes For Permit 19120499 |
| Permit Number |
19120499 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2020-08-19 07:54:55 | PROVISO = | | | 1) WILL NEED TO PROVIDE SIGNED AND SEALED LOUVER SYSTEM | | | DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. FBC 1609 | | | 2) WILL NEED TO PROVIDE SIGNED AND SEALED METAL CANOPY | | | DETAILS TO COMPLY WITH THE DESIGN WIND LOADS. FBC 1609 | | | 3) WILL NEED TO PROVIDE A SIGNED AND SEALED SOIL REPORT | | | (GEOTECHNICAL REPORT) TO VERIFY THE REQUIRED SOIL | | | BEARING CAPACITY PER NOTES ON THE DRAWINGS. |
|