| 2020-04-30 12:42:44 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NEED TO ADD AN OUTLET AT THE SERVICE LOCATION PER | | | 210.64 | | | | | | 210.64 ELECTRICAL SERVICE AREAS AT LEAST ONE 125-VOLT, | | | SINGLE-PHASE, 15- OR 20-AMPERE-RATED RECEPTACLE OUTLET | | | SHALL BE INSTALLED WITH IN 15 M (50 FT) OF THE | | | ELECTRICAL SERVICE EQUIPMENT. | | | | | | 2) NEED AIC CALCULATION AND LABLES FOR SERVICE | | | EQUIPMENT. 110.24 | | | | | | 110.24 AVAILABLE FAULT CURRENT ( A) FIELD MARKING. | | | SERVICE EQUIPMENT IN OTHER THAN DWELLING UNITS SHALL BE | | | LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE | | | FAULT CURRENT. THE FIELD MARKING(S) SHALL INCLUDE THE | | | DATE THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE | | | OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT | | | INVOLVED | | | | | | 3) INTERSYSTEM BONDING CONNECTION TO BE INSTALLED AT | | | SERVICE. 250.94 | | | | | | 250.94 BONDING FOR OTHER SYSTEMS AN INTERSYSTEM BONDING | | | TERMINATION FOR CONNECTING INTERSYSTEM BONDING | | | CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED | | | EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT OR | | | METERING EQUIPMENT ENCLOSURE AND AT THE DISCONNECTING | | | MEANS FOR ANY ADDITIONAL BUILDINGS OR STRUCTURES. |
|