| Plan Review Notes For Permit 19120499 |
| Permit Number |
19120499 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-02-03 12:30:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET 2.0 - THERE ARE TWO EXIT DOORS, ONE FROM EACH | | | BUILDING, INDICATED AS SWINGING OUT ONTO TO A COVERED | | | CORRIDOR. | | | | | | THE DOOSR OPEN INTO A PATH OF EGRESS AND NOT IN | | | COMPLIANCE WITH NFPA 101, CH 7 MEANS OF EGRESS. | | | | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE | | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT | | | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A | | | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, | | | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | | WIDTH OF THE STAIR LANDING WHEN THE DOOR | | | LEAF IS FULLY OPEN. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|