| 2020-01-14 14:36:42 | SIGN BUILDING REVIEW CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | 1- SIGN ENGINEER OF RECORD NEEDS TO CLARIFY SIGN | | | MOUNTING CONDITIONS. BASED ON CITY RECORDS, THE COLUMNS | | | SHOWN ON PLANS SUBMITTED ARE PRECAST DECORATIVE COLUMNS | | | TO COVER THE STRUCTURAL STEEL COLUMNS. DRAWINGS | | | SUBMITTED SHOW ATTACHMENT OF THE SIGN TO THE DECORATIVE | | | PRECAST COLUMN. ENGINEERING CALCULATIONS SUBMITTED | | | SPECIFY POURED CONCRETE AS THE MOUNTING SURFACE | | | CONSTRUCTION. SIGN ENGINEER TO CLARIFY/VERIFY THAT | | | CALCULATIONS SUBMITTED APPLIES TO THE DECORATIVE | | | PRECAST COLUMN. SEC. 1609.1 FBC-BUILDING. SEC. | | | 107.2.1.2 CITY AMENDMENTS. | | | | | | 2- ANCHOR TYPE AND SIZE SPECIFIED BY THE ENGINEER ON | | | THE DESIGN LOAD CALCULATIONS FOR MOUNTING CONDITION | | | METHOD 4 DOESN'T MATCH ANCHOR SPECIFIED ON SHEET 2 OF | | | 3. CLARIFY/REVISE. SEC. 1609.1 FBC-BUILDING. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | | | | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE | | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | | COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|