| Plan Review Notes For Permit 19120455 |
| Permit Number |
19120455 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-01-17 08:22:37 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1. OK | | | | | | 2. OK | | | | | | 3. FAIL, STILL PENDING: | | | | | | FBC B 107.2.1, THE SPA DETAIL ON SHEET 4 OF 5 OF THE | | | ROOF TOP SPA PLAN HAS A REFERENCE TO THE STRUCTURAL | | | HOUSE PLANS FOR AREA UNDER SPA SHELL. THE HOUSE PLAN | | | (PERMIT # 17021032) DETAIL 2 OF PAGE S?7 REFERENCES | | | GLASS JACUZZI AND CONNECTIONS BY DELEGATED ENGINEER. | | | PLEASE PROVIDE CONNECTIONS WITH ENGINEERED CALCULATIONS | | | AND WATER/MOISTURE BARRIER DETAILS /SPECIFICATIONS. |
|