| 2019-12-23 16:06:57 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1. FBC R 4501.17, PROVIDE ON SITE PLAN THE LOCATION OF | | | BARRIERS FOR POOL AND ROOF TOP (NON PORTABLE) SPA. | | | 2. FBC R 312.1, INDICATE ON ROOF TOP SITE PLAN THE | | | LOCATIONS AND DETAILS/SPECIFICATIONS OF GUARDS AND SET | | | BACK MEASUREMENTS. | | | 3. FBC B 107.2.1, THE SPA DETAIL ON SHEET 4 OF 5 OF THE | | | ROOF TOP SPA PLAN HAS A REFERENCE TO THE STRUCTURAL | | | HOUSE PLANS FOR AREA UNDER SPA SHELL. THE HOUSE PLAN | | | (PERMIT # 17021032) DETAIL 2 OF PAGE S-7 REFERENCES | | | GLASS JACUZZI AND CONNECTIONS BY DELEGATED ENGINEER. | | | PLEASE PROVIDE CONNECTIONS WITH ENGINEERED CALCULATIONS | | | AND WATER/MOISTURE BARRIER DETAILS /SPECIFICATIONS. |
|