| 2020-02-24 10:40:22 | PLUMBING COMMENTS: APPROVED WITH PROVISO | | | 1. PROVIDE VENT TO BUILDING EXTERIOR TO COMPLY WITH THE | | | REQUIREMENTS OF FBC PL 904.1. VENT INSTALLATION SHALL | | | COMPLY WITH FBC PL 905.2, 905.3, 905.4, 905.5 AND | | | 906.1. | | | 2. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE | | | AS A DEFERRED SUBMITTAL, TWO (2) COPIES OF | | | MANUFACTURER?S SPECIFICATION/DATA SHEET FOR AN ASSE | | | 1070 COMPLIANT TANKLESS WATER HEATER. | | | |
|