| 2019-12-31 14:11:30 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: |
| | 1. PER WPB FBC 107.2.1 AND 107.3.5.1.5, PROVIDE |
| | MANUFACTURER SPECIFICATION AND SCHEDULE FOR THE GAS |
| | TANKLESS WATER HEATERS. INDICATE WHETHER THEY ARE NEW |
| | OR EXISTING. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE |
| | ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) FBC FG |
| | 502 THRU 505. |
| | 2. PER WPB FBC 107.2.1 AND 107.3.5.1.5, PROVIDE |
| | MANUFACTURER SPECIFICATION FOR THE COOK LINE EQUIPMENT. |
| | 3. PER WPB FBC 107.2.1 AND 107.3.5.1.5, PROVIDE |
| | DETAILED PIPING FLOOR PLAN AND RISER DIAGRAM THAT ARE |
| | CONSISTENT WITH EACH OTHER. SHOW LOCATION OF EMERGENCY |
| | SHUT OFF VALVE. IDENTIFY THE APPLIANCES ON THE FLOOR |
| | PLAN CORRESPONDING WITH THE RISER DIAGRAM. RISER |
| | DIAGRAM SHOWS TWO WATER HEATERS, FLOOR PLAN SHOWS |
| | THREE. CLARIFY. SHOW LOCATION OF GAS METER/REGULATOR ON |
| | THE FLOOR PLAN. |
| | 4. PER WPB FBC 107.2.1 AND 107.3.5.1.5, SUBMIT |
| | CALCULATIONS FOR COMBUSTION AIR PER FBC FG 304.1 |
| | 5. RE: GAS LOAD CALCULATIONS; PER WPB FBC 107.2.1 AND |
| | 107.3.5.1.5, LIST THE BTU LOAD OF EACH APPLIANCE AND |
| | PROVIDE THE QUANTITY OF EACH. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19120428 1540 PALM BEACH LAKES BLVD # 100 |