| 2019-12-16 15:39:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET C 1 & 1.1A - THERE ARE INDICATIONS OF AN |
| | EXISTING HOOD SYSTEM. THE EXISTING HOOD SYSTEM SHALL |
| | HAVE CURRENT CERTIFICATIONS OF FUNCTION AND CLEANING AT |
| | THE TIME OF FIRE INSPECTION. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROPER DOCUMENTATION. |
| | |
| | PLEASE ADD A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | 2) SHEET 1.6A - IN THE OCCUPANCY LOAD TABLE THERE ARE |
| | INDICATION OF A BANQUET BENCH WITH 38. |
| | |
| | THERE ARE 16 SPACES OPPOSITE THE INDICATED CHAIRS |
| | APPROX. 8 MORE SPACES FOR SITTING FOR TOTAL OF 24. |
| | |
| | THERE ARE ALSO NO DIMENSION OF THE THE LENGHT OF THE |
| | BENCH. |
| | |
| | PLEASE REVIEW AND CORRECT OF JUSTIFY ALL 38 SPACES |
| | |
| | |
| | 3) SHEET 1.6A - IN THE OCCUPANCY LOAD TABLE THERE ARE |
| | INDICATION OF A BAR WITH 19. |
| | |
| | THERE ARE 10 BAR STOOLS ALONG THE BAR AREA.. |
| | |
| | THERE ARE ALSO NO DIMENSION OF THE THE LENGHT OF THE |
| | BAR, |
| | |
| | PLEASE REVIEW AND CORRECT OF JUSTIFY ALL 19 STOOLS. |
| | |
| | |
| | 4) SHEET 1.6A - THE OUTSIDE AREA DOES NOT HAVE |
| | DIMENSION TO JUSTIFY THE SEATING ARRANGEMENT ALONG THE |
| | OUTSIDE WALL. |
| | |
| | PER NFPA 101, CH 12 NEW ASSEMBLY OCCUPANCIES THERE DOES |
| | NOT APPEAR ENOUGH ROOM FOR THIS PROPOSED ARRANGEMENT. |
| | |
| | 12.2.5.7* AISLE ACCESSWAYS SERVING SEATING AT TABLES. |
| | |
| | 12.2.5.8 AISLES SERVING SEATING AT TABLES. |
| | |
| | PLEASE REVIEW AND PROVIDE ALL DIMENSION AND INDICATE |
| | AND ENSURE PROPER DIMENSION BETWEEN TABLES, CHAIRS AND |
| | AISLES SHOWING COMPLIANCE. |
| | |
| | |
| | 5) SHEET 1.6A - THE INSIDE AREAS DO NOT HAVE DIMENSION |
| | TO JUSTIFY THE SEATING ARRANGEMENTS. |
| | |
| | PER NFPA 101, CH 12 NEW ASSEMBLY OCCUPANCIES THERE DOES |
| | NOT APPEAR ENOUGH ROOM FOR THIS PROPOSED ARRANGEMENT. |
| | |
| | 12.2.5.7* AISLE ACCESSWAYS SERVING SEATING AT TABLES. |
| | |
| | 12.2.5.8 AISLES SERVING SEATING AT TABLES. |
| | |
| | PLEASE REVIEW AND PROVIDE ALL DIMENSIONS AND INDICATE |
| | AND ENSURE PROPER DIMENSION BETWEEN TABLES, CHAIRS AND |
| | AISLES SHOWING COMPLIANCE. |
| | |
| | |
| | 6) SHEET 1.7A - DOOR # 1 WITHIN THE DOOR SCHEDULE |
| | INDICATES A DEAD-BOLT LOCK BUT DOES NOT INDICATE PANIC |
| | HARDWARE. |
| | |
| | PER NFPA 101, CH 12 ND CH 7 MEANS OF EGRESS. |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE |
| | PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| | IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| | UNLESS |
| | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | LOCKS AS |
| | PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| | ACCESS-CONTROLLED EGRESS DOORS |
| | AS PERMITTED IN 12.2.2.2.6. |
| | 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| | SHALL BE PERMITTED |
| | TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| | IF BOTH OF THE |
| | FOLLOWING CONDITIONS APPLY: |
| | (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| | AND THE ASSEMBLY |
| | OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| | (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| | ASSEMBLY |
| | OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE |
| | RELEASED |
| | BY PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | |
| | |
| | PLEASE REVIEW, AND PROVIDE A NOTE OF ACKNOWLEDEMENT OF |
| | ALL CONDITIONS OR CORRECT. |
| | |
| | |
| | 7) SHEET 1.7A - DOOR # 5 WITHIN THE DOOR SCHEDULE |
| | INDICATES PUSH/PULL/CLOSER BUT DOES NOT A LOCK/LATCH |
| | NOR INDICATE PANIC HARDWARE. |
| | |
| | PER NFPA 101, CH 12 ND CH 7 MEANS OF EGRESS. |
| | |
| | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| | AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE |
| | PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| | IS PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| | UNLESS |
| | OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| | LOCKS AS |
| | PERMITTED IN 12.2.2.2.5. |
| | (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| | ACCESS-CONTROLLED EGRESS DOORS |
| | AS PERMITTED IN 12.2.2.2.6. |
| | 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| | SHALL BE PERMITTED |
| | TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| | IF BOTH OF THE |
| | FOLLOWING CONDITIONS APPLY: |
| | (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| | AND THE ASSEMBLY |
| | OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| | (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| | ASSEMBLY |
| | OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE |
| | RELEASED |
| | BY PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT. |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |