Plan Review Notes
Plan Review Notes For Permit 19120428
Permit Number 19120428
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-12-16 15:39:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET C 1 & 1.1A - THERE ARE INDICATIONS OF AN
 EXISTING HOOD SYSTEM. THE EXISTING HOOD SYSTEM SHALL
 HAVE CURRENT CERTIFICATIONS OF FUNCTION AND CLEANING AT
 THE TIME OF FIRE INSPECTION.
  
 PLEASE ENSURE COMPLIANCE AND PROPER DOCUMENTATION.
  
 PLEASE ADD A NOTE OF ACKNOWLEDGEMENT.
  
  
 2) SHEET 1.6A - IN THE OCCUPANCY LOAD TABLE THERE ARE
 INDICATION OF A BANQUET BENCH WITH 38.
  
 THERE ARE 16 SPACES OPPOSITE THE INDICATED CHAIRS
 APPROX. 8 MORE SPACES FOR SITTING FOR TOTAL OF 24.
  
 THERE ARE ALSO NO DIMENSION OF THE THE LENGHT OF THE
 BENCH.
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY ALL 38 SPACES
  
  
 3) SHEET 1.6A - IN THE OCCUPANCY LOAD TABLE THERE ARE
 INDICATION OF A BAR WITH 19.
  
 THERE ARE 10 BAR STOOLS ALONG THE BAR AREA..
  
 THERE ARE ALSO NO DIMENSION OF THE THE LENGHT OF THE
 BAR,
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY ALL 19 STOOLS.
  
  
 4) SHEET 1.6A - THE OUTSIDE AREA DOES NOT HAVE
 DIMENSION TO JUSTIFY THE SEATING ARRANGEMENT ALONG THE
 OUTSIDE WALL.
  
 PER NFPA 101, CH 12 NEW ASSEMBLY OCCUPANCIES THERE DOES
 NOT APPEAR ENOUGH ROOM FOR THIS PROPOSED ARRANGEMENT.
  
 12.2.5.7* AISLE ACCESSWAYS SERVING SEATING AT TABLES.
  
 12.2.5.8 AISLES SERVING SEATING AT TABLES.
  
 PLEASE REVIEW AND PROVIDE ALL DIMENSION AND INDICATE
 AND ENSURE PROPER DIMENSION BETWEEN TABLES, CHAIRS AND
 AISLES SHOWING COMPLIANCE.
  
  
 5) SHEET 1.6A - THE INSIDE AREAS DO NOT HAVE DIMENSION
 TO JUSTIFY THE SEATING ARRANGEMENTS.
  
 PER NFPA 101, CH 12 NEW ASSEMBLY OCCUPANCIES THERE DOES
 NOT APPEAR ENOUGH ROOM FOR THIS PROPOSED ARRANGEMENT.
  
 12.2.5.7* AISLE ACCESSWAYS SERVING SEATING AT TABLES.
  
 12.2.5.8 AISLES SERVING SEATING AT TABLES.
  
 PLEASE REVIEW AND PROVIDE ALL DIMENSIONS AND INDICATE
 AND ENSURE PROPER DIMENSION BETWEEN TABLES, CHAIRS AND
 AISLES SHOWING COMPLIANCE.
  
  
 6) SHEET 1.7A - DOOR # 1 WITHIN THE DOOR SCHEDULE
 INDICATES A DEAD-BOLT LOCK BUT DOES NOT INDICATE PANIC
 HARDWARE.
  
 PER NFPA 101, CH 12 ND CH 7 MEANS OF EGRESS.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 7.2.1.5.5 KEY-OPERATED LOCKS.
 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE
 PERMITTED TO HAVE
 KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11
 THROUGH 43 FOR
 THE SPECIFIC OCCUPANCY.
 (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS
 FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF:
 THIS
 DOOR TO REMAIN UNLOCKED WHEN THE
 BUILDING IS OCCUPIED.
 (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY
 DISTINGUISHABLE
 AS LOCKED.
 (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT
 INSIDE THE
 BUILDING WHEN IT IS LOCKED.
  
  
 PLEASE REVIEW, AND PROVIDE A NOTE OF ACKNOWLEDEMENT OF
 ALL CONDITIONS OR CORRECT.
  
  
 7) SHEET 1.7A - DOOR # 5 WITHIN THE DOOR SCHEDULE
 INDICATES PUSH/PULL/CLOSER BUT DOES NOT A LOCK/LATCH
 NOR INDICATE PANIC HARDWARE.
  
 PER NFPA 101, CH 12 ND CH 7 MEANS OF EGRESS.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT.
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  