2020-01-23 14:31:21TENANT BUILD-OUT, REVISION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS
  
 ORIGINAL COMMENT:
 1- WATER CLOSET IN REVISED RESTROOM #108 NEED TO BE
 LOCATED IN THE CORNER, DIAGONAL TO THE DOOR. REVISE AS
 REQUIRED BY SEC 213.3.1 AND SEC 604.8.1.7
 FBC-ACCESSIBILITY.
  
 RESPONSE:
 A) DISCUSSED PROPOSED TOILET LAYOUT WITH ROBERT BROWN
 (BUILDING OFFICIAL). PROPOSED LAYOUT SHOWN ON THE
 ENLARGED TOILET PLAN MAY WORK WITH SEC. 604.3.2
 FBC-ACCESSIBILITY FOR OVERLAPPING OF CLEARANCES, BUT IS
 MISSING INFORMATION. PLEASE PROVIDE WRITTEN DIMENSIONS
 FOR ALL REQUIRED CLEARANCES. SPECIFY THE DIMENSIONS FOR
 THE DOOR MANEUVERING CLEARANCES, SPECIFY THE 60"
 TURNING CIRCLE AND THE CLEARANCES FOR THE WATER CLOSET.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) ALL PLANS SUBMITTED UNDER THIS REVISION NEED TO BE
 REVISED SHOWING THE PROPOSED LAYOUT. THERE ARE SOME
 PLANS THAT WERE NOT REVISED TO REFLECT THE PROPOSED
 CHANGES. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  