| Plan Review Notes For Permit 19120420 |
| Permit Number |
19120420 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-01-23 14:31:21 | TENANT BUILD-OUT, REVISION SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS | | | | | | ORIGINAL COMMENT: | | | 1- WATER CLOSET IN REVISED RESTROOM #108 NEED TO BE | | | LOCATED IN THE CORNER, DIAGONAL TO THE DOOR. REVISE AS | | | REQUIRED BY SEC 213.3.1 AND SEC 604.8.1.7 | | | FBC-ACCESSIBILITY. | | | | | | RESPONSE: | | | A) DISCUSSED PROPOSED TOILET LAYOUT WITH ROBERT BROWN | | | (BUILDING OFFICIAL). PROPOSED LAYOUT SHOWN ON THE | | | ENLARGED TOILET PLAN MAY WORK WITH SEC. 604.3.2 | | | FBC-ACCESSIBILITY FOR OVERLAPPING OF CLEARANCES, BUT IS | | | MISSING INFORMATION. PLEASE PROVIDE WRITTEN DIMENSIONS | | | FOR ALL REQUIRED CLEARANCES. SPECIFY THE DIMENSIONS FOR | | | THE DOOR MANEUVERING CLEARANCES, SPECIFY THE 60" | | | TURNING CIRCLE AND THE CLEARANCES FOR THE WATER CLOSET. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | B) ALL PLANS SUBMITTED UNDER THIS REVISION NEED TO BE | | | REVISED SHOWING THE PROPOSED LAYOUT. THERE ARE SOME | | | PLANS THAT WERE NOT REVISED TO REFLECT THE PROPOSED | | | CHANGES. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|