Plan Review Notes
Plan Review Notes For Permit 19120420
Permit Number 19120420
Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-14 09:27:001ST REVIEW:19120420
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE DOOR FOR BATHROOM #108 IS DIRECTLY IN FRONT OF
 THE TOILET THAT IS A CODE VIOLATION. DOORS SHALL BE
 LOCATED IN THE FRONT PARTITION OR IN THE SIDE WALL OR
 PARTITION FARTHEST FROM THE WATER CLOSET. WHERE LOCATED
 IN THE FRONT PARTITION, THE DOOR OPENING SHALL BE 4
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION FARTHEST
 FROM THE WATER CLOSET. PER FBC ACC 604.8.1.2
  
 2.WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX. PER FBC PL
 403.2
  
 3. SHT. A-501 DETAIL E-08G1 THE REAR WALL GRAB BAR
 SHALL BE 36 INCHES LONG MINIMUM AND EXTEND FROM THE
 CENTERLINE OF THE WATER CLOSET 12 INCHES MINIMUM ON ONE
 SIDE AND 24 INCHES MINIMUM ON THE OTHER SIDE. PER FBC
 ACC 604.5.2
  
 4. SHT. A-501 DETAIL E-08G2 HAS A NOTE NOT USED PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  