| 2020-01-13 14:50:06 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19120409 |
| | ADD: 3200 N. MILITARY TRAIL |
| | CONT: KAST |
| | TEL: 561-689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JAN. 13TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 3 OF 5: |
| | |
| | 1A) DESIGN NOTES, SPECIFICALLY: PALM BEACH COUNTY: 3 |
| | SECOND GUST OF 150 MPH RISK CATEGORY 1 STRUCTURE. THE |
| | JOBSITE IS LOCATED WITHIN THE CITY OF WEST PALM BEACH |
| | JURISDICTION, NOT PALM BEACH COUNTY, PLEASE UPDATE |
| | PLANS. |
| | |
| | 1B) THE TYPICAL SIDE ELEVATION SHOWS THE TYPICAL |
| | RAFTER, NOT CLEAR IF THIS DIMENSIONAL LUMBER 4X4 OR 4 |
| | INCH ROUND TIMBERS? THE 2ND ISSUE IS THE PLANS DO NOT |
| | INDICATE AT WHAT THE DIMENSION IS CENTER TO CENTER? THE |
| | 3RD QUESTION IS THE ANCHORING OF THE TYPICAL RAFTER TO |
| | THE RIDGE OR THE PERIMETER HEADER? |
| | |
| | 1C) THE FRONT CUT SECTION DOES NOT MAKE CLEAR IF THE 6 |
| | INCH ROUND FRAME SUPPORT IS TO BE THE ONLY SUPPORT. THE |
| | PLAN SPECIFICALLY STATES THIS SUPPORT IS FOR A CEILING |
| | FAN. THE CUT SECTION DOES NOT SHOW ANY RAFTER TIES/ |
| | WIND TIES/ COLLAR TIES. THE FRONT/ SECTION DOES NOT |
| | SHOW THE USE OF CEILING JOIST TO HOLD THE EXTERIOR |
| | WALLS FROM BOWING OUT. PLEASE SHOW COMPLIANCE WITH THE |
| | 2017 FBC-B SECTION: |
| | |
| | 2017 FBC-B 2308.7.3.1 CEILING JOIST AND RAFTER |
| | CONNECTIONS. WHERE CEILING JOISTS ARE NOT PARALLEL TO |
| | RAFTERS, AN EQUIVALENT RAFTER TIE SHALL BE INSTALLED IN |
| | A MANNER TO PROVIDE A CONTINUOUS TIE ACROSS THE |
| | BUILDING, AT A SPACING OF NOT MORE THAN 4 FEET (1219 |
| | MM) ON CENTER. THE CONNECTIONS SHALL BE IN ACCORDANCE |
| | WITH TABLES 2308.7.3.1 AND 2304.10.1, OR CONNECTIONS OF |
| | EQUIVALENT CAPACITIES SHALL BE PROVIDED. RAFTER TIES |
| | SHALL BE SPACED NOT MORE THAN 4 FEET ON CENTER. RAFTER |
| | TIE CONNECTIONS SHALL BE BASED ON THE EQUIVALENT RAFTER |
| | SPACING IN TABLE 2308.7.3.1. |
| | |
| | 2) PLEASE NOTE THE SUBMITTED INSTALLATION INSTRUCTIONS |
| | FOR EITHERTHE ALOHA OR BORA BORA SYNTHETIC LEAF ROOF |
| | SYSTEM. THE SUBMITTED BROCHURE STATES THE FRAMING |
| | MEMBERS THAT THIS SYNTHETIC LEAF ROOF SYSTEM IS TO |
| | ATTACHED IS A MAXIMUM SPACING OF 19 5/8 INCH/ 50 CM. |
| | PLEASE PROVIDE IF THE RAFTER SPACING LISTED ABOVE IN |
| | COMMENT 1B WILL MEET THIS REQUIREMENT, OR WILL THERE BE |
| | A NEED FOR PERLINS? THE OTHER ISSUE THE SPACING FOR |
| | ROWS AFTER THE 1ST ROW IS TO BE 4 3/8 INCH FOR THIS |
| | SYNTHETIC LEAF ROOF SYSTEM, PLEASE ADD THE SPACING |
| | INFORMATION OF THE ROWS ON THE PLANS IN CASE THE |
| | INSTALLATION SPECS DO NOT MAKE IT TO THE JOB. 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |