| Date |
Text |
| 2020-01-30 14:20:33 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. THE LOAD CALCULATION PROVIDED DOES |
| | NOT MEET CODE. THE DEMAND FACTORS CANNOT BE APPLIED |
| | TWICE. THE CALCULATION PROVIDED APPLIES DEMAND FACTORS |
| | TO PANEL K AND THEN USES THAT NUMBER AND APPOIES DEMAND |
| | FACTORS AGAIN FOR PANEL MDP. PROVIDE CORRECTION. NEC |
| | 215.2, 220, 408.30; FBC RE E3602.2 (IN YOUR RESPONSE |
| | LETTER, THIS COMMENT WAS ADDRESSED SATISFACTORILY. |
| | HOWEVER, THIS CORRECTION DID NOT MAKE IT ONTO THE PLAN. |
| | PROVIDE CORRECTION TO THE PLAN TO MATCH THE EXPLANATION |
| | IN THE LETTER.) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |