| Plan Review Notes For Permit 19120396 |
| Permit Number |
19120396 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-07-13 13:12:24 | PLAN DENIED | | | 1) PROVIDE DUCT SIZE, GRILL SIZE AND CFM ON ALL SUPPLY | | | DUCT AND | | | GRILL SIZE AND DUCT SIZE ON ALL RETURN AIR DUCT.SECTION | | | 107 FBC 2017 | | | 2) PLEASE PROVIDE MORE INFORMATION ON AIR CONDITIONING | | | EQUIPMENT | | | IF EXISTING MARK EXISTING ON PLAN BY EQUIPMENT. IF NEW | | | EQUIPMENT | | | PROVIDE EQUIPMENT SCHEDULE ON PLAN.SECTION 107 FBC 2017 | | | 3) PROVIDE EXHAUST FOR BATHROOMS TABLE M1507.4 | | | RESIDENTIAL CODE 2017 | | | 4) RETURN AIR IS NOT REQUIRED IN LAUNDRY ROOMS OR | | | CLOSETS SECTION M 1602.3 | | | BALANCED RETURN AIR EXCEPTION # 3 RESIDENTIAL CODE 2017 | | | 5) PROVIDE MASTER RETURN AIR FOR AIR CONDITIONING 1 AND | | | 2 | | | 6) SIGNATURE IS REQUIRED ON THE PLAN. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|