| 2019-12-16 07:29:34 | 12/16/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SCOPE OF WORK IS NOT CLEAR OF WHAT IS BEING DONE ON |
| | YOU PLUMBING PAGE. PLEASE GIVE A DESCRIPTIVE NARRATIVE |
| | OF WHAT IS IN AND WHAT IS BEING REPLACED PER THE FBC |
| | WPB A 101.2. |
| | 2. IN TITLE PLEASE SHOW THE CODE YEAR OR REFENCE TO |
| | WHICH YOU ARE REGULATING AS IT SHALL BE KNOWN AS THE |
| | FLORIDA BUILDING CODE HEREINAFTER REFERRED TO AS "THIS |
| | CODE" PER THE FBC WPB A 101.1. |
| | 3. A SUB PLUMBING PERMIT IS REQUIRED FOR THE SCOPE OF |
| | WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | 4. PLUMBING RISER DIAGRAM REQUIRED WPB AMENDMENTS TO |
| | THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING. |
| | 5. A SET OF PLANS HAS BEEN SUBMITTED THAT IS DRAWN IN |
| | PENCIL. PLANS DONE IN PENCIL ARE UNACCEPTABLE AS THE |
| | DRAWING CAN BE MODIFIED/CHANGED. WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1.4 QUALITY OF BUILDING PLANS. |
| | 6. YOU HAVE SUBMITTED ONLY ONE SET OF PLANS, TWO PLANS |
| | ARE REQUIRED PER THE FBC WPB A 107.1. |
| | 7. PLEASE SHOW HOT WATER HEATING EQUIPMENT ON PLUMBING |
| | PAGE AND IF YOU ARE USING A ANY TYPE OF GAS EQUIPMENT |
| | PLEASE NOTE ON PLANS AND SUBMIT MANUFACTURES |
| | SPECIFICATION FOR THEM PER THE 2017 FBC R 2722.2. |
| | 8. A GAS STOVE IS SHOWN ON PLANS A GAS PERMIT ALONG |
| | WITH AN EVALUATION IS REQUIRED IS USING GAS AS THE CITY |
| | DOES NOT SHOW A PERMIT ON FILE FOR GAS PER THE 2017 FBC |
| | WPB A 107.1. |
| | 9. CLEAN-OUT OUTSIDE OF BUILDING SHALL BE WITHIN 10' |
| | PLEASE SHOW DISTANCE PER THE 2017 FBC R3005.2.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |