| 2020-01-06 14:50:56 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19120396 |
| | 1/6/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SIX COPIES OF AN ARCHITECTURAL FLOOR PLAN DRAWING |
| | HAVE BEEN MARKED UP IN PENCIL AND SUBMITTED EACH |
| | BEARING SHEET NUMBER A-001. PLANS DRAWN IN PENCIL ARE |
| | NOT ACCEPTABLE, AND EACH PLAN SHEET SHALL BE NUMBERED |
| | DIFFERENTLY- SECTION 107.2.1 WPB. |
| | |
| | 2) THE SUBMITTED MECHANICAL PLAN HAS NUMEROUS |
| | DEFICIENCIES.THE RESUBMITTED, CORRECTED MECHANICAL PLAN |
| | SHALL BE DRAWN LEGIBLY, SHALL BEAR THE SIGNATURE OF THE |
| | PERSON WHO PREPARED THE DRAWING- SECTION 107.2.1 WPB. |
| | PLEASE INCLUDE THE FOLLOWING INFORMATION AND DETAILS ON |
| | THE DRAWINGS: |
| | |
| | A) A CLEARLY WRITTEN SCOPE OF WORK FOR MECHANICAL |
| | ALTERATIONS. IT APPEARS ALL NEW SYSTEMS AND DUCTWORK |
| | HAVE BEEN INSTALLED- SECTION 107.2.1.2 WPB. |
| | |
| | B) SUPPLY AND RETURN DUCT SIZES- SECTION M1601.1 & |
| | M1602.3 FBC RES. |
| | |
| | C) DIFFUSER AND RETURN GRILL SIZES AND CFMS BEING |
| | SUPPLIED AT EACH DIFFUSER- SECTION M1601.1 FBC RES. |
| | |
| | D) AC EQUIPMENT SCHEDULES- M1401.3 FBC RES. |
| | |
| | E) AIR HANDLER AND CONDENSER LOCATIONS AND INSTALLATION |
| | DETAILS- M1401.1 & M1305.1.4.1 FBC RES. |
| | |
| | F) CONDENSATE DISPOSAL DETAILS- PRIMARY CONDENSATE |
| | PIPING RUNS AND DISCHARGE LOCATIONS. SECONDARY |
| | CONDENSATE DISPOSAL DETAILS- SECTION M1411.3.1 FBC RES |
| | |
| | 3) SUBMIT AC COOLING AND HEATING CALCULATIONS IN |
| | ACCORDANCE WITH ACCA MANUAL J- SECTION R403.6.1 FBC EC. |
| | |
| | 4) SUBMIT AHRI CERTIFICATES FOR THE NEW AC SYSTEMS- |
| | SECTION R501.7 FBC EC. |
| | |
| | 5) A FL. LICENSED MECHANICAL CONTRACTOR SHALL SUBMIT A |
| | SUB-PERMIT FOR THE WORK PER FL. STATUE 489. PLEASE NOTE |
| | THAT ANY PERSON INSTALLATING OR SERVICING AC EQUIPMENT |
| | SHALL BE EPA CERTIFIED TO HANDLE REFRIGERANTS- SECTION |
| | 608 USEPA. |
| | |
| | 6) IT APPEARS FLEX DUCTS MAY BE INSTALLED IN THE GARAGE |
| | WHICH IS NOT ALLOWED PER SECTION R302.5.2 FBC RES |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |