2020-01-06 14:50:561ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19120396
 1/6/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SIX COPIES OF AN ARCHITECTURAL FLOOR PLAN DRAWING
 HAVE BEEN MARKED UP IN PENCIL AND SUBMITTED EACH
 BEARING SHEET NUMBER A-001. PLANS DRAWN IN PENCIL ARE
 NOT ACCEPTABLE, AND EACH PLAN SHEET SHALL BE NUMBERED
 DIFFERENTLY- SECTION 107.2.1 WPB.
  
 2) THE SUBMITTED MECHANICAL PLAN HAS NUMEROUS
 DEFICIENCIES.THE RESUBMITTED, CORRECTED MECHANICAL PLAN
 SHALL BE DRAWN LEGIBLY, SHALL BEAR THE SIGNATURE OF THE
 PERSON WHO PREPARED THE DRAWING- SECTION 107.2.1 WPB.
 PLEASE INCLUDE THE FOLLOWING INFORMATION AND DETAILS ON
 THE DRAWINGS:
  
 A) A CLEARLY WRITTEN SCOPE OF WORK FOR MECHANICAL
 ALTERATIONS. IT APPEARS ALL NEW SYSTEMS AND DUCTWORK
 HAVE BEEN INSTALLED- SECTION 107.2.1.2 WPB.
  
 B) SUPPLY AND RETURN DUCT SIZES- SECTION M1601.1 &
 M1602.3 FBC RES.
  
 C) DIFFUSER AND RETURN GRILL SIZES AND CFMS BEING
 SUPPLIED AT EACH DIFFUSER- SECTION M1601.1 FBC RES.
  
 D) AC EQUIPMENT SCHEDULES- M1401.3 FBC RES.
  
 E) AIR HANDLER AND CONDENSER LOCATIONS AND INSTALLATION
 DETAILS- M1401.1 & M1305.1.4.1 FBC RES.
  
 F) CONDENSATE DISPOSAL DETAILS- PRIMARY CONDENSATE
 PIPING RUNS AND DISCHARGE LOCATIONS. SECONDARY
 CONDENSATE DISPOSAL DETAILS- SECTION M1411.3.1 FBC RES
  
 3) SUBMIT AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH ACCA MANUAL J- SECTION R403.6.1 FBC EC.
  
 4) SUBMIT AHRI CERTIFICATES FOR THE NEW AC SYSTEMS-
 SECTION R501.7 FBC EC.
  
 5) A FL. LICENSED MECHANICAL CONTRACTOR SHALL SUBMIT A
 SUB-PERMIT FOR THE WORK PER FL. STATUE 489. PLEASE NOTE
 THAT ANY PERSON INSTALLATING OR SERVICING AC EQUIPMENT
 SHALL BE EPA CERTIFIED TO HANDLE REFRIGERANTS- SECTION
 608 USEPA.
  
 6) IT APPEARS FLEX DUCTS MAY BE INSTALLED IN THE GARAGE
 WHICH IS NOT ALLOWED PER SECTION R302.5.2 FBC RES
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  