Plan Review Notes
Plan Review Notes For Permit 19120396
Permit Number 19120396
Review Stop G
Sequence Number 1
Notes
Date Text
2020-07-27 10:56:5807/27/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM, WHAT IS THE DRYERS, STOVE AND
 HEATER, LABEL ON ISOMETRIC. REFER TO THE 2017 FBC-RES.
 SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1) THROUGH
 G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES ARE
 USED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
  
 5. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS AND OR
 INSTALLATION INSTRUCTIONS FOR THE GAS DRYER, HEATER AND
 STOVE. THE GAS APPLIANCE SHALL BE LISTED AND LABELED
 PER THE 2017 FBC FG RES. SEC. G2404.3. THE
 MANUFACTURER'S SPECIFICATIONS SHALL NOTE THE CFM'S THAT
 ARE BEING EXHAUSTED BY THE DRYER AND BTU FOR EACH
 APPLIANCE.
  
 6. A SUB GAS PERMIT IS REQUIRED FOR THE SCOPE OF WORK
 PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT STOVE,
 TANKLESS AND DRYER) TO VERIFY COMPLIANCE WITH 2017 FBC
 RES. SEC. G2408.1.
  
 8. PLACE A NOTE ON BOTH SETS OF PLANS LISTING THE
 SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD THAT
 WERE USED IN THE DESIGN OF THIS SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.3.
  
 9. LABEL SHUTOFF VALVE, DRIP LEG, REGULATOR AND UNIONS
 ON GAS ISOMERIC PER THE 2017 FBC RES. SEC. G2401.1.3.
  
 10. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLANS THIS A 2 LBS SYSTEM OR .5 LBS SYSTEM (12?
 W.C.) PLEASE LABEL ON ISOMETRIC PER THE WPB AMEND. TO
 FBC SEC. 107.2.1.
  
 11. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 12. MOST TANKLESS UNITS CALL FOR 10.5? WATER COLUMN AND
 THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
  
 13. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FG SEC. 304.1, 614.5 (CLOTHES DRYERS AND STROVE) OR
 2017 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 14. IF LOUVER ARE BEING USED FOR COMBUSTION AIR PLEASE
 SHOW THE SIZE OF THE LOUVER(S) AND LOCATION ON THE
 PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 15. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 16. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS
 FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC
 107.2.1, 107.3.5
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  