| 2020-07-27 10:56:58 | 07/27/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES. |
| | SECS. G2413.4.1, G2413.4.2. |
| | |
| | 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM, WHAT IS THE DRYERS, STOVE AND |
| | HEATER, LABEL ON ISOMETRIC. REFER TO THE 2017 FBC-RES. |
| | SEC. G2413.3, G2413.4 AND TABLES G2413.4 (1) THROUGH |
| | G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES ARE |
| | USED. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| | FBC-RES. SEC. G 2413.4.1, G2413.4.2. |
| | |
| | 5. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS AND OR |
| | INSTALLATION INSTRUCTIONS FOR THE GAS DRYER, HEATER AND |
| | STOVE. THE GAS APPLIANCE SHALL BE LISTED AND LABELED |
| | PER THE 2017 FBC FG RES. SEC. G2404.3. THE |
| | MANUFACTURER'S SPECIFICATIONS SHALL NOTE THE CFM'S THAT |
| | ARE BEING EXHAUSTED BY THE DRYER AND BTU FOR EACH |
| | APPLIANCE. |
| | |
| | 6. A SUB GAS PERMIT IS REQUIRED FOR THE SCOPE OF WORK |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 7. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT STOVE, |
| | TANKLESS AND DRYER) TO VERIFY COMPLIANCE WITH 2017 FBC |
| | RES. SEC. G2408.1. |
| | |
| | 8. PLACE A NOTE ON BOTH SETS OF PLANS LISTING THE |
| | SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD THAT |
| | WERE USED IN THE DESIGN OF THIS SYSTEM PER THE 2017 FBC |
| | RES. SEC. G2413.3. |
| | |
| | 9. LABEL SHUTOFF VALVE, DRIP LEG, REGULATOR AND UNIONS |
| | ON GAS ISOMERIC PER THE 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | 10. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLANS THIS A 2 LBS SYSTEM OR .5 LBS SYSTEM (12? |
| | W.C.) PLEASE LABEL ON ISOMETRIC PER THE WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | |
| | 11. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 12. MOST TANKLESS UNITS CALL FOR 10.5? WATER COLUMN AND |
| | THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 13. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC FG SEC. 304.1, 614.5 (CLOTHES DRYERS AND STROVE) OR |
| | 2017 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| | DRYERS). |
| | |
| | 14. IF LOUVER ARE BEING USED FOR COMBUSTION AIR PLEASE |
| | SHOW THE SIZE OF THE LOUVER(S) AND LOCATION ON THE |
| | PLANS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 15. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 16. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND |
| | SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS |
| | FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE. |
| | PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC |
| | 107.2.1, 107.3.5 |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |