2020-01-03 10:29:35BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19120396
 REVIEWED: JANUARY 3, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 107.5.3 FBC[AMENDED] 107.2.1FBC[AMENDED] ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 - PLEASE ADD SIGNATURE OF RESPONSIBLE PARTY TO ALL
 PLANS. ALSO, PROVIDE A SECOND SET OF PLANS.
  
 2) 107.5.3 FBC[AMENDED] ADD CODE EDITION TO STATE
 CURRENT BUILDING CODE THAT APPLIES TO NEW WORK. (2017
 FLORIDA BUILDING CODE 6TH EDITION)
 -
  
 3) 107.3.5 FBC[AMENDED]DEMO SHEET A-001.
 - SHOW AREA WHERE DEMO OR IN-FILL IS OCCURING. FOR
 EXAMPLE THE MASTER BEDROOM WALL LOOKS LIKE IT IS BEING
 REMOVED TO ADD A ADDITIONAL FRENCH DOORS. HIGHLIGHT
 SECTION OF WALL TO REMOVE, ADD NOTE AND PROVIDE DETAIL
 OF HOW THE STRUCTURE ABOVE IS SUPPORTED.
  
 4) 107.3.5 FBC[AMENDED]DEMO SHEET A-001.
 - PROVIDE DETAILS OF HOW WALL IS BEING IN-FILLED AND
 HOW OPENINGS ARE BEING ENLARGED TO ACCOMMODATE NEW
 WINDOWS.
  
 5) 107.3.5 FBC[AMENDED]DEMO SHEET A-001.
 - IS THERE ANY WORK PERFORMED IN THE AREA LABELED
 EFFICIENCY? IF NO WORK IS BEING PERFORMED IN THE
 EFFICIENCY, HATCH THAT AREA AND STATE NO WORK BEING
 PERFORMED.
  
 6) 301.1 FBC[EXISTING] GENERAL. THE REPAIR, ALTERATION,
 CHANGE OF OCCUPANCY, ADDITION OR RELOCATION OF ALL
 EXISTING BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS
 LISTED IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED
 BY THE APPLICANT. SECTIONS 301.1.1 THROUGH 301.1.3
 SHALL NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
 A) 301.1.1 FBC[EXISTING] PRESCRIPTIVE COMPLIANCE
 METHOD. REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF
 OCCUPANCY COMPLYING WITH CHAPTER 4 OF THIS CODE IN
 BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 B) 301.1.2 FBC[EXISTING] WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 5 THROUGH 13 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
 C) 301.1.3 FBC[EXISTING] PERFORMANCE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 14 OF
 THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
 - WHICH METHOD IS BEING USED FOR COMPLIANCE?
 (PRESCRIPTIVE,WORK AREA COMPLIANCE OR PERFORMANCE)
  
 7) 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
 - IF WORK AREA COMPLIANCE PLEASE ADD LEVEL OF
 ALTERATION TO DESIGN DATA. THIS WOULD BE A LEVEL 3
 ALTERATION.
  
 8) R314.2.2 FBC[R] ALTERATIONS, REPAIRS AND ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 - SHOW LOCATIONS OF SMOKE ALARMS TO MEET REQUIREMENTS
 FOR NEW CONSTRUCTION.
  
 R314.3 FBC[R] LOCATION. SMOKE ALARMS SHALL BE INSTALLED
 IN THE FOLLOWING LOCATIONS:
  
 A. IN EACH SLEEPING ROOM.
  
 B. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 C. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
  
 D. SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.
  
 R314.3.1 FBC[R] INSTALLATION NEAR COOKING APPLIANCES.
 SMOKE ALARMS SHALL NOT BE INSTALLED IN THE FOLLOWING
 LOCATIONS UNLESS THIS WOULD PREVENT PLACEMENT OF A
 SMOKE ALARM IN A LOCATION REQUIRED BY SECTION R314.3.
  
 A. IONIZATION SMOKE ALARMS SHALL NOT BE INSTALLED LESS
 THAN 20 FEET (6096 MM) HORIZONTALLY FROM A PERMANENTLY
 INSTALLED COOKING APPLIANCE.
  
 B. IONIZATION SMOKE ALARMS WITH AN ALARM-SILENCING
 SWITCH SHALL NOT BE INSTALLED LESS THAN 10 FEET (3048
 MM) HORIZONTALLY FROM A PERMANENTLY INSTALLED COOKING
 APPLIANCE.
  
 C. PHOTOELECTRIC SMOKE ALARMS SHALL NOT BE INSTALLED
 LESS THAN 6 FEET (1828 MM) HORIZONTALLY FROM A
 PERMANENTLY INSTALLED COOKING APPLIANCE.
  
 R314.4 FBC[R] INTERCONNECTION. WHERE MORE THAN ONE
 SMOKE ALARM IS REQUIRED TO BE INSTALLED WITHIN AN
 INDIVIDUAL DWELLING UNIT IN ACCORDANCE WITH SECTION
 R314.3, THE ALARM DEVICES SHALL BE INTERCONNECTED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE ALARM WILL
 ACTIVATE ALL OF THE ALARMS IN THE INDIVIDUAL DWELLING
 UNIT. PHYSICAL INTERCONNECTION OF SMOKE ALARMS SHALL
 NOT BE REQUIRED WHERE LISTED WIRELESS ALARMS ARE
 INSTALLED AND ALL ALARMS SOUND UPON ACTIVATION OF ONE
 ALARM. EXCEPTION: INTERCONNECTION OF SMOKE ALARMS IN
 EXISTING AREAS SHALL NOT BE REQUIRED WHERE ALTERATIONS
 OR REPAIRS DO NOT RESULT IN REMOVAL OF INTERIOR WALL OR
 CEILING FINISHES EXPOSING THE STRUCTURE, UNLESS THERE
 IS AN ATTIC, CRAWL SPACE OR BASEMENT AVAILABLE THAT
 COULD PROVIDE ACCESS FOR INTERCONNECTION WITHOUT THE
 REMOVAL OF INTERIOR FINISHES.
  
 R314.5 FBC[R] COMBINATION ALARMS. COMBINATION SMOKE AND
 CARBON MONOXIDE ALARMS SHALL BE PERMITTED TO BE USED IN
 LIEU OF SMOKE ALARMS.
  
 9) R315.1.1 FBC[R] CARBON MONOXIDE ALARM. THE
 REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED BY
 PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS:
  
 A. A HARD-WIRED CARBON MONOXIDE ALARM.
  
 B. A BATTERY-POWERED CARBON MONOXIDE ALARM.
  
 C. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
  
 D. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
  
 R315.1.2 FBC[R] COMBINATION ALARMS. COMBINATION
 SMOKE/CARBON MONOXIDE ALARMS SHALL BE LISTED AND
 LABELED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 10) R609.7.2.1 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE. WHERE THE WOOD SHIM OR BUCK THICKNESS IS
 LESS THAN 11/2 INCHES (38 MM), WINDOW AND GLASS DOOR
 ASSEMBLIES SHALL BE ANCHORED THROUGH THE JAMB, OR BY
 JAMB CLIP AND ANCHORS SHALL BE EMBEDDED DIRECTLY INTO
 THE MASONRY, CONCRETE OR OTHER SUBSTANTIAL SUBSTRATE
 MATERIAL. ANCHORS SHALL ADEQUATELY TRANSFER LOAD FROM
 THE WINDOW OR DOOR FRAME INTO THE ROUGH OPENING
 SUBSTRATE [SEE FIGURES R609.7.2(1) AND R6097.2(2)].
 - PROVIDE DETAIL OF DOOR/WINDOW BUCK.
  
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS 11/2 INCHES
 (38 MM) OR MORE, THE BUCK IS SECURELY FASTENED TO THE
 MASONRY, CONCRETE OR OTHER SUBSTANTIAL SUBSTRATE, AND
 THE BUCK EXTENDS BEYOND THE INTERIOR FACE OF THE WINDOW
 OR DOOR FRAME, WINDOW AND GLASS DOOR ASSEMBLIES SHALL
 BE ANCHORED THROUGH THE JAMB, OR BY JAMB CLIP, OR
 THROUGH THE FLANGE TO THE SECURED WOOD BUCK. ANCHORS
 SHALL BE EMBEDDED INTO THE SECURED WOOD BUCK TO
 ADEQUATELY TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME
 ASSEMBLY [SEE FIGURES R609.7.2(3), R6097.2(4) AND
 R609.7.2(5)].
 - PROVIDE DETAIL OF WINDOW INSTALL, OR REFER TO PRODUCT
 APPROVAL INSTALLATION INSTRUCTIONS.
  
 11) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS:
 GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED
 PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY
 SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE.
  
 12) 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT
 ARE PART OF THE ALTERATION SHALL COMPLY WITH SECTION
 R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH
 R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5
  
 13) 807.2 FBC[E]NEW STRUCTURAL ELEMENTS. NEW STRUCTURAL
 ELEMENTS IN ALTERATIONS, INCLUDING CONNECTIONS AND
 ANCHORAGE, SHALL COMPLY WITH THE FLORIDA BUILDING CODE,
 BUILDING.
  
 14) PROVIDE WINDOW AND DOOR SCHEDULES TO SHOW WINDOW
 LOCATIONS AND SIZES. SCHEDULE CAN CORESPOND WITH MARKS
 ON PLAN VIEW.
  
 15) 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR
 WINDOWS, DOORS, GARAGE DOOR, CLADDING AND COMPONENTS.
  
 16) ASCE 7-10 26.7.1 PLEASE ADD PROJECT DATA TO PLANS.
 OCCUPANCY = R3
 TYPE OF WALL CONSTRUCTION = ARE THE WALLS MASONRY,
 CONCRETE OR WOOD FRAMED?
 RISK CATEGORY = II
 EXPOSURE CATEGORY = B
 BUILDING CLASSIFICATION = ENCLOSED
 MEAN BLDG. HGT. = 0?-0? THIS WILL BE THE HEIGHT
 MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF
 PEAK.
 WIND SPEED V ULT = 170
 WIND SPEED V ASD = 132
 ALSO, STATE THE EXISTING SQ. FOOTAGE CONDITIONED AND
 NON CONDITIONED. STATE THE NEW SQ. FOOTAGE CONDITIONED
 AND NON CONDITIONED.
  
 17) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR WINDOWS, MULL BETWEEN FRENCH DOORS AND DOORS.
 - THE NOA'S ARE LISTED ON THE SALES SHEETS, BUT WE NEED
 THE ACTUAL NOA'S PRINTED OUT WITH TWO COPIES.
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  