| 2020-01-14 17:06:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19120391 |
| | 1/14/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS- SECTION C403.2.1 FBC EC. |
| | |
| | 2) SUBMIT AN ENERGY COMPLIANCE REPORT- SEE SECTIONS |
| | C101.2, C101.5.1 AND C401.2 FBC EC. |
| | |
| | 3) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED |
| | PER SECTION C408.2 FBC EC. SUBMIT A COMMISSIONING PLAN |
| | AS OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN |
| | SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE THAT A COPY |
| | OF THE COMMISSIONING REPORT SHALL BE SUBMITTED FOR |
| | REVIEW AT FINAL INSPECTION. |
| | |
| | 4) M1 & M2: CORRECT THE M5 REFERENCE FOR THE MECHANICAL |
| | ROOM TO M2 SECTION 107.2.1 WPB. |
| | |
| | 5) M1: PROVIDE A DUCT SMOKE DETECTOR SYMBOL IN THE |
| | SUPPLY SYSTEM OF AHU-1- SECTION 606.2.1 FBC M. |
| | |
| | 6) M1: SHOW RETURN AIR FROM STORAGE ROOMS 103 & 105- |
| | SECTION 601.6 FBC M. |
| | |
| | 7) M1: EXHAUST VENTILATION IS REQUIRED FOR THE DRESSING |
| | ROOM AT A RATE OF 0.25 CFMS PER SF.- TABLE 403.3.1.1 |
| | FBC M. |
| | |
| | 8) M2: THE VENTILATION CALCULATIONS FOR AUDITORIUM ARE |
| | INCORRECT. TABLE 403.3.1.1 FBC M REQUIRES 150 PERSONS |
| | PER 1000 SF. |
| | |
| | 9) PROVIDE ENGINEERING FOR INSTALLATION OF THE CHILLER- |
| | SECTION 301.15 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |