| 2020-01-28 12:54:08 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19120391 |
| | ADD: 4850 FRED GLADSTONE DR. |
| | CONT: THE WHITING-TURNER CO. |
| | TEL: 954-536-9251 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JAN. 28TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| | ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO. |
| | 4504-14, AND CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| | DEVELOPMENT. |
| | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 2) THE PERMIT APPLICATION INDICATES THE DOLLAR AMOUNT |
| | OF $2,500,000.00 DOLLARS IN VALUE. THIS MAIN BUILDING |
| | PERMIT WILL INCLUDE THE FEES FOR THE MECHANICAL, |
| | ELECTRICAL, PLUMBING & ROOFING PERMITS. WHEN THE |
| | GENERAL CONTRACTOR COMES IN FOR A BUILDING PERMIT WITH |
| | THE SIGNED PERMIT APPLICATION FORM BY THE QUALIFIER AND |
| | OWNER AND BRINGS IN THE LISTED SUB-PERMITS M-E-P & |
| | ROOFING PERMITS SIGNED BY THE QUALIFIER OF EACH |
| | COMPANY, THEIR INSURANCES AND LICENSURE UP TO DATE, THE |
| | M-E-P AND ROOFING PERMITS ARE FREE OF CHARGE. IF THE |
| | M-E-P & ROOFING PERMITS COME IN LATER THERE WILL BE AN |
| | $80.00 ADMINISTRATIVE FEE FOR EACH PERMIT. |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 3) THIS BUILDING DOES NOT QUALIFY AS A THRESHOLD |
| | BUILDING BUT COULD BE CONSIDERED FOR THE RESIDENT |
| | INSPECTOR PROGRAM UNDER SECTION 110.3.9 OF THE WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, 6TH |
| | EDITION (2017) CHAPTER 1, ADMINISTRATION CODE. THE |
| | ALTERNATIVE IS USING THE CITY INSPECTORS FOR |
| | INSPECTIONS, I?VE SPOKEN KEN CONRAD CHIEF BUILDING |
| | INSPECTOR IF HE HAD ANY PREFERENCE. IF THE CONTRACTOR |
| | WAS PUSHED WITH MULTIPLE BUILDING INSPECTIONS EACH DAY |
| | BECAUSE OF TIME CONSTRAINTS THE RESIDENT INSPECTOR |
| | MAYBE PREFERRED. IF YOU WOULD PREFER TO USE THE CITY |
| | INSPECTORS FOR THE STRUCTURAL PORTION OF THE BUILDING |
| | PLEASE REVIEW THE LIMITATIONS OF OUR STAFF FOR WELDED |
| | OR BOLTED CONNECTIONS. |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| | AMERICAN WELDING SOCIETY. |
| | 2017 FBC-B 2204.1 WELDING |
| | 2017 FBC-B 2204.2 BOLTING. |
| | FOR THESE TYPES OF CONNECTIONS A 3RD PARTY |
| | CERTIFICATION WOULD BE REQUIRED. IF THERE IS ANY |
| | QUESTIONS ABOUT THE CODE REQUIREMENTS FOR THIS SECTION, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. PLEASE LET US KNOW YOUR INTENTIONS, IF |
| | YOU DECIDE TO USE A RESIDENT INSPECTOR WE WILL SEND THE |
| | FORMS TO YOU BY E-MAIL, WE JUST NEED TO KNOW YOUR |
| | INTENTIONS. THANK YOU. |
| | |
| | 4) SHEET S-3 UNDER THE HEADING FOUNDATION NOTE 1.A |
| | INDICATES THERE IS A SOILS REPORT DATED 08/14/19 BY |
| | TERRACON. IF THEY CAN UPLOAD THE REPORT WITH ELECTRONIC |
| | SIGNATURES WITH THE NEXT SUBMITTAL GREAT. IF THEY NEED |
| | TO SUBMIT PAPER REPORT WITH ORIGINAL SIGNATURE AND SEAL |
| | THAT WILL WORK ALSO. 2017 FBC-B 1803.5.2 QUESTIONABLE |
| | SOIL. WHERE THE CLASSIFICATION, STRENGTH OR |
| | COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A |
| | LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| | PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| | BE CONDUCTED. |
| | |
| | 5) NO ACTION REQUIRED. SHEET S-4 WIND PRESSURES ARE |
| | GOOD FOR ROOF ZONES FOR FLAT 1,2,3, SLOPED 6,7,8 AND |
| | WALL ZONES 4 & 5. |
| | |
| | 6) THIS REVIEW THERE WERE NO PRODUCT APPROVALS |
| | SUBMITTED. IF EITHER THE DESIGNER OF RECORD OR THE |
| | GENERAL CONTRACTOR WOULD PREFER TO HAVE THE BAR JOIST & |
| | PRODUCT APPROVAL FOR COMPONENTS AND CLADDING DEFERRED |
| | PLEASE NOTE SO FOR THE NEXT SUBMITTAL. 107.3.4.2 |
| | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 6A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 6B) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT |
| | APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 6C) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 7) ON BOTH ARCHITECTURAL SHEETS A-5.2 & A-5.3 AND THE |
| | STRUCTURAL SHEETS S-6, S-7 & S-8 ALL SLOPED ROOF |
| | SECTIONS SHOW THE USE OF 5/8 INCH CDX PLYWOOD. PLEASE |
| | REFER BACK TO THE 2017 FBC-B SECTION 603.1.1.1.3 ROOF |
| | CONSTRUCTION INCLUDING GIRDERS, TRUSSES FRAMING & |
| | DECKING NEED TO BE FIRE-RETARDANT TREATED WOOD. THIS IS |
| | FOR BOTH TYPE I & TYPE II CONSTRUCTION. SECTION 718.5 |
| | FOR CONCEALED SPACES, EXCEPTION 1 REFERS BACK TO |
| | COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION 603. |
| | |
| | 8) SHEET A-5.2 WALL SECTION B, THE LIFE SAFETY SHEET |
| | DECLARES THIS SECTION OF THE ADDITION AS TYPE I-B |
| | CONSTRUCTION. IN THE 2017 FBC-B TABLE 601 FOR TYPE I-B |
| | CONSTRUCTION, THE ROOF CONSTRUCTION AND ASSOCIATED |
| | SECONDARY MEMBERS REQUIRES A 1 HOUR FIRE RATING OF THE |
| | LIGHT GAUGE METAL TRUSSES BEING INSTALLED IN THIS AREA. |
| | |
| | 9) SHEET A-5.2 WALL SECTION B HAS A NOTE FOR THE 2 HOUR |
| | RATED CEILING SEE A-9.0 DETAIL # 5. THIS DETAIL IS FOR |
| | A 2 HOUR FIRE RATED SHAFT WALL DESIGN, UL DESIGN U-415 |
| | SYSTEM B. THIS SYSTEM U-415 IS A TESTED WALL ASSEMBLY, |
| | TO BE USED VERTICALLY, THAT IS HOW IT WAS TESTED. YOU |
| | WILL NEED TO FIND A CEILING ASSEMBLY WITH A 2 HOUR FIRE |
| | RATING. |
| | |
| | 10) SHEET A-5.2 DETAIL B INDICATES THE INSTALLATION OF |
| | ICYNENE SPRAY INSULATION. PLEASE SUBMIT THE ICC-ES OR |
| | ERS REPORT AND CIRCLE WHICH APPLICATION WILL BE USED |
| | SEE 4.0 DESIGN AND INSTALLATION. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. SHOW COMPLIANCE WITH |
| | 2603.4.1.6 ATTICS, THE FOAM INSULATION SHALL BE |
| | PROTECTED AGAINST IGNITION. THIS BARRIER IS TO COVER |
| | THE FOAM INSULATION. |
| | |
| | 11) SHEET A-1.0 SHOWS THE STAGE 1 FOOT HIGHER THAN THE |
| | FLOOR AUDITORIUM. IT APPEARS IN THE DETAIL 7/ A-8.1 THE |
| | STAGE IS CONCRETE BASED. NEITHER THE ARCHITECTURAL NOR |
| | STRUCTURAL SHEETS PROVIDE THE HEIGHT OF THE MID-LANDING |
| | OF THE ACCESSIBLE RAMP. 2017 FBC-ACCESSIBILITY CODE |
| | SECTION 405.2. RAMP RUNS SHALL HAVE A SLOPE NOT STEEPER |
| | THAN 1:12. |
| | |
| | 12) SHEET A-1. SHOWS A DETAIL 3A & 3B /A-6.3 PANTRY |
| | WALL 104 WITH A MICROWAVE ON A SHELF. THE TOP OF THE |
| | SHELF IS AT 48 INCHES ABOVE THE FLOOR. MUST COMPLY WITH |
| | THE 2017 ACCESSIBILITY CODE SECTIONS: |
| | |
| | 12A) 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1 |
| | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE |
| | REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH |
| | REACH. |
| | |
| | 12B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS |
| | SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL |
| | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| | MAXIMUM. |
| | |
| | 13) THIS REVIEW CYCLE THERE WAS NO ENERGY CODE REPORTS |
| | SUBMITTED. 2017 FBC-ENERGY CODE. C401.2 APPLICATION. |
| | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| | FOLLOWING: |
| | 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING |
| | SECTION 9.4.1.1(G) OF THE STANDARD. |
| | 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN |
| | ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| | SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| | SECTION C406.1.1. |
| | 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| | C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING |
| | ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT |
| | OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | |
| | 14) - DIGITAL SUBMITTALS: PLANS WILL BE REVIEWED BY THE |
| | PBC IMPACT FEE OFFICE DIGITALLY VIA PROJECT DOX UPON |
| | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR |
| | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE |
| | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY |
| | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO |
| | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE |
| | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: |
| | HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| | YOUR PROJECT OR EMAIL IT TO [email protected] . |
| | PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 |
| | N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. |
| | |
| | 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |