Plan Review Notes
Plan Review Notes For Permit 19120386
Permit Number 19120386
Review Stop P
Sequence Number 1
Notes
Date Text
2019-12-31 12:12:301ST REVIEW: 19120386
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. TS-1 IN THE RESTROOM FIXTURE CALCULATION ARE
 INCORRECT UNDER THE MENS IT SHOULD BE 1 PER 150 NOT 1
 PER 75. PER FBC PL TABLE 403.1 A3
  
 2.GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. PER FBC ACC 609.4
  
 3. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. PER FBC ACC 603.3
  
 4. SHT.TS-1 THE RESTROOM FIXTURE CALCULATIONS ARE
 LISTING 2 TOILETS , 1 LAVATORY FOR WOMEN 2 TOILETS, 1
 LAVATORY FOR MEN THE FLOOR PLAN SHOWS 3 TOILETS, 3
 LAVATORY'S FOR MEN AND 3 TOILETS, 3 LAVATORY'S FOR
 WOMEN PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT-0.1 SHOWS DETAILS FOR SHOWERS NO SHOWERS ARE
 SHOWN ON THE PLAN PLEASE CLARIFY OR REMOVE ANY DETAILS
 THAT ARE NOT BEING USED. PER WPB AMEND TO FBC 107.2.1
  
 6. SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION. THE
 WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION,
  
 7. SHT. A-2.3 SHOW COMPLIANCE WITH FBC ACC 603.3
 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 8. AT LEAST ONE OF THE LAVATORY'S OUTSIDE OF THE
 ACCESSIBLE STALL SHALL COMPLY WITH FBC ACC 213.3.4,
 606.2, 606.3
  
 9. SHT.P-1.0 THE SANITARY ISOMETRIC AND FLOOR PLAN IS
 SHOWING A HORIZONTAL DRY VENT WHICH IS A CODE VIOLATION
 EACH TOILET SHOULD CONNECT TO THE BRANCH DRAIN
 SEPARATELY AND COMPLY WITH FBC PL 905.3, 905.4, 914.1
  
 10. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 11. A WATER FOUNTAIN IS REQUIRED. PER FBC PL TABLE
 403.1
  
 12. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1
  
 13. ON THE WATER ISOMETRIC SHUT OFF VALVES ARE REQUIRED
 ON ALL THE HOT AND COLD DROPS. PER FBC PL 606.1(5)
  
 14. A HOT WATER RECIRCULATION SYSTEM IS REQUIRED THE
 DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, FROM
 THE SOURCE OF HOT WATER TO THE FIXTURES THAT REQUIRE
 HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET (15 240
 MM). RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING
 SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED
 WATER. PER FBC PL 607.2
  
 END OF COMMENTS
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]