| 2019-12-31 12:12:30 | 1ST REVIEW: 19120386 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. TS-1 IN THE RESTROOM FIXTURE CALCULATION ARE |
| | INCORRECT UNDER THE MENS IT SHOULD BE 1 PER 150 NOT 1 |
| | PER 75. PER FBC PL TABLE 403.1 A3 |
| | |
| | 2.GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE. PER FBC ACC 609.4 |
| | |
| | 3. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. PER FBC ACC 603.3 |
| | |
| | 4. SHT.TS-1 THE RESTROOM FIXTURE CALCULATIONS ARE |
| | LISTING 2 TOILETS , 1 LAVATORY FOR WOMEN 2 TOILETS, 1 |
| | LAVATORY FOR MEN THE FLOOR PLAN SHOWS 3 TOILETS, 3 |
| | LAVATORY'S FOR MEN AND 3 TOILETS, 3 LAVATORY'S FOR |
| | WOMEN PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHT-0.1 SHOWS DETAILS FOR SHOWERS NO SHOWERS ARE |
| | SHOWN ON THE PLAN PLEASE CLARIFY OR REMOVE ANY DETAILS |
| | THAT ARE NOT BEING USED. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION. THE |
| | WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION, |
| | |
| | 7. SHT. A-2.3 SHOW COMPLIANCE WITH FBC ACC 603.3 |
| | MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 8. AT LEAST ONE OF THE LAVATORY'S OUTSIDE OF THE |
| | ACCESSIBLE STALL SHALL COMPLY WITH FBC ACC 213.3.4, |
| | 606.2, 606.3 |
| | |
| | 9. SHT.P-1.0 THE SANITARY ISOMETRIC AND FLOOR PLAN IS |
| | SHOWING A HORIZONTAL DRY VENT WHICH IS A CODE VIOLATION |
| | EACH TOILET SHOULD CONNECT TO THE BRANCH DRAIN |
| | SEPARATELY AND COMPLY WITH FBC PL 905.3, 905.4, 914.1 |
| | |
| | 10. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 11. A WATER FOUNTAIN IS REQUIRED. PER FBC PL TABLE |
| | 403.1 |
| | |
| | 12. A SERVICE SINK IS REQUIRED. PER FBC PL TABLE 403.1 |
| | |
| | 13. ON THE WATER ISOMETRIC SHUT OFF VALVES ARE REQUIRED |
| | ON ALL THE HOT AND COLD DROPS. PER FBC PL 606.1(5) |
| | |
| | 14. A HOT WATER RECIRCULATION SYSTEM IS REQUIRED THE |
| | DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, FROM |
| | THE SOURCE OF HOT WATER TO THE FIXTURES THAT REQUIRE |
| | HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET (15 240 |
| | MM). RECIRCULATING SYSTEM PIPING AND HEAT-TRACED PIPING |
| | SHALL BE CONSIDERED TO BE SOURCES OF HOT OR TEMPERED |
| | WATER. PER FBC PL 607.2 |
| | |
| | END OF COMMENTS |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |